5-6
B-04: Set Battery Capacity
This setting controls battery charging amperages and other settings. The factory
setting for CAPACITY is 1600 amp hours for SC-80 MPPT and 3200 amp
hours for SC-160X MPPT.
At full output capacity a SC-80 MPPT can deliver 80 amps to a battery, this
amount of amperage (current) is equal to the C/10 (capacity divided by ten) rate
of a 1600 amp hour battery and, as such meets most manufacturers
recommendations for minimum PV charging capacity.
In applications with battery banks under 1600 amp hours it is recommended to
lower the Maximum Charge Rate setting from the default 80 amps to the C10
rate of the battery bank.
B-05: BAT. MAX Charge Amps
Use Constant B-05 to allow the installer to limit the maximum charge amps
allowed to the batteries. The factory setting is 80 amps (SC-80 MPPT) and 160
amps (SC-160X MPPT).
B-06: Set Absorption Volts
Use Constant B-06 to adjust the Absorption voltages. The default values are
based on the battery type and capacity selected. It is not advisable to change
default settings unless advised by the battery manufacturer or supplier.
Battery Type
Absorption Volts
Range
Factory
Setting
FLOODED
13.9V~15.2V
14.6V
AGM
13.7V~15.1V
14.1V
GEL
13.6V~15.1V
14.1V
The above values are based on 12V system. The values x 2 are for 24V
system; the values x 3 are for 36V system and the values x 4 are for 48V
system.
OPTI-Solar SC MPPT Series will charge at the Absorption voltage and at the length
of time before switching to float mode.
Summary of Contents for SC-160X MPPT
Page 7: ...VII Dimension for SC 50 MPPT Unit mm Fig 1...
Page 8: ...VIII Dimension for SC 80 MPPT Dimension for SC 80X MPPT Unit mm Fig 2...
Page 9: ...IX Dimension for SC 160X MPPT Unit mm Fig 3...
Page 12: ...1 3 Fig 4...
Page 20: ...3 2 3 2 The following is the Initialization Stage Flow Chart OTPI Solar SC 80 MPPT V0 9311...
Page 27: ...3 9 Main Menu Programming Group F Menu Group Constants Constants Edit Data Enter...
Page 28: ...3 10 Main Menu Programming Group O Menu Group Constants Constants Edit Data Enter...
Page 29: ...3 11 Main Menu Data Log Menu Constants Constants Edit Data Enter...