ACK21-01A
ontracactuators.com
60
Function setting of
status output contact
BA1 setting
Special menu for Ontrac
service personnel only
BA2 output setting
BA8 output setting
Factory service only
The two digits on left side of “_” in the value area are the function code. The actuator
has up to eight switching value output ports BA1~BA8, and each port can be
arbitrarily set to one of the 20 functions of “01” ~ “20” function (see the table below),
The right side of “_” can be set to “0” or “1”, “0” represents the off state when the
contact is not triggered, and “1” presents the on state when the contact is not
triggered. Set the function with and set the trigger mode with .
01 Ready to run
02 Failure alarm
03 Open to the end position
04 Close to the end position
05 Exceeded torque in “OPEN” direction
06 Exceeded torque in “CLOSE” direction
07 Intermediate valve position indication 1
08 Intermediate valve position indication 2
09 Remote control
10 Local control
11 Actuator operation (continuous signal)
12 Actuator operation (pulse signal)
13 Operation indication in “OPEN” direction (pulse signal)
Valve end position indication (continuous signal)
14 Operation indication in “CLOSE” direction (pulse signal)
Valve end position indication (continuous signal)
15 Analog / Digital value control indication
16 Operation indication in “OPEN” direction (continuous signal)
17 Operation indication in “CLOSE” direction (continuous signal)
18 ESD state indication (continuous signal)
19 Hand crank state indication (press in indication)
20 Analog signal loss alarm
Useful part per menu P5.8
Basic: BA1~BA4 effective
385: BA1~BA8 effective
387: BA1~BA7 effective