-8-
in “DEGREE” or write “2” if you want the alarm when the
temperature rises
above
the alarm temperature.
4.
Set active temperature sensor (EXTTEMP)
(see page 20).
1)
If you have an external temp sensor (optional) and you want it to
control the temperature alarm and thermostat you have to activate it.;
Create a new contact and name it EXTTEMP.
i.
In the telephone number field write ”1”.
5.
Active the function “relay activates at alarms” (ALARMRELAY)
(see page
1)
Create a new contact and name it “ALARMRELAY”.
i.
In the telephone number field write ”1”
6.
Activate delay for ”Power failure alarm” ( POWERFAIL)
(see page 26).
1)
If an internal backup battery (optional) has been connected the unit
alarms when the ordinary power is disconnected. It is possible to set a
delay for this alarm.
2)
Create a new contract and name it ”POWERFAIL”.
i.
In the telephone number field, write the number of minutes
delay you want (1-40 is allowed)
ii.
If the digit ”0” (zero) is set the function will be deactivated.
7.
Activation of the GPSFENCE
(see page 24).
1)
If a GPS receiver (optional) has been connected you can set it to send
an alarm if the unit has been moved from its original position. You can
set at which distance from the original position you want the unit to
send an alarm.
2)
Create a new contact and name it ”GPSFENCE”.
i.
In the telephone number field write alarm distance in
multiples of 50 meters.
Example: If you want an alarm when the unit has moved 300
meters away from the original position, write the digit “6”
(6*50=300). If you want to set 900 meters write 18
(18*50=900).