FT-3100 TRANSMITTER PROGRAMMING GUIDE
ONICON Incorporated 727.447.6140
Page 28
onicon.com
Digital Output 1 Function Select
[Out1 = XXXXXX]
Digital Output 2 Function Select
[Out2 = XXXXXX]
mA Output 1 Function & Scaling
[Out mA1 = 4_20 +/-]
Analog Output 1 Full Scale Value
[A1S = Gal/m XXXXXX]
Digital Output 1
Function Select
[Out1 = XXXXXX]
Digital Output 2
Function Select
[Out2 = XXXXXX]
Digital Output Functions
OFF: Disables output
MAX AL+: Maximum forward flow rate alarm (Energized = no alarm)
MIN AL+: Minimum forward flow rate alarm (Energized = no alarm)
MAX/MIN+: Maximum or minimum forward flow rate alarms (Energized = no alarm)
MAX AL-: Maximum reverse flow rate alarm (Energized = no alarm)
MIN AL-: Minimum reverse flow rate alarm (Energized = no alarm)
MAX/MIN-: Maximum or minimum reverse flow rate alarms (Energized = no alarm)
MAX/MIN +/-: Maximum and minimum flow rate alarm, either direction (Energized = no alarm)
P. EMPTY: Empty pipe alarm output (Energized = no alarm)
HARDW.AL.: Master alarm for open coil, empty pipe or measurement error (Energized = no alarm)
OVERFLOW: Flow out of range alarm (Energized = no alarm)
ALL ALARMS: Activates when any alarm is active (Energized = no alarm)
EXT. COMM.: Allows the pulse output state (high or low) to be set via MODBUS
F.R. SIGN: Flow direction indication (Energized = reverse (-) flow)
*SCALE: Indicates which scale is active (Energized = Scale2)
FREQ+: Frequency output proportional to forward (+) direction flow rate
FREQ-: Frequency output proportional to reverse (-) direction flow rate
FREQ+/-: Frequency output to forward (+) / reverse (-) direction flow rate
: Scaled pulse output for forward (+) direction flow rate
PULSES-: Scaled pulse output for reverse (-) direction flow rate
/-: Scaled pulse output for forward (+) / reverse (-) direction flow rate
*This function is only available when either the autorange [Autorange= OFF] function in menu 4 or the
change flow range via pulse input [Range change= OFF] function INPUTS (MENU 6 are active.
To change the setting, press enter to access the function. Use the up and right arrow keys to change
the setting. Press enter to accept the change and exit the function. Press escape to exit the program
mode.
The available functions for digital output 1 are listed in the table below.
The available functions for digital output 2 are listed in the table below.
3.7 MENU 7 - OUTPUTS