background image

 

 

2015-01-07 

 

 

Page 3/9 

be connected to the internal terminals. If a 

number of slave units are connected to the 

KSUA, the first and last units must be 

terminated by closing jumper I in the KSUG or 

jumper PL2 in the KSUA. Sometimes, the 

KSUA is between other units, and in this case 

both the terminations are in KSUGs. Note that 

there cannot be more than two terminations in 

the whole network. The maximum line length 

is 1200m without repeater. 

Addressing 

 

Jumper settings for address 5. 

 

A KSUG will only work in the network if an 

address is defined. The jumpers numbered 

1,2,4,8 and 16 are used to configure the 

address. For example to use address 15, close 

jumpers 1,2,4 and 8 (1+2+4+8=15). You 

cannot use the same address for two units 

within the same network. The addresses go 

from 0 to 31. To set address 0, leave all jumper 

1,2,4,8 and 16 empty. Dampers and detectors 

are counted from address 0 upwards. For 

example address 0 DMP1+2. Address 1 

DMP3+4. Address 3 SPJ5+6 etc. (two 

dampers per address) 

Description of jumpers in network 

mode. 

Jumper  On 

Off 

1,2,4,8,16  Address configuration 

BSIA BR24-F-ST  RFT MANF 

VD24 

RFT MANF 

VM24 

Controlled by 

jumper F 

Stand-alone mode  Network mode 

Choice of damper actuator. 

Jumper F and G selects the actuator type to be 

used. If jumper F is ON, Belimo BSIA24 and 

BR24-F-ST. If jumper G is on RFT MANF 

VM24 type is selected. If both jumper F and G 

is off RFT MANF VD24 is selected. 

Smoke detectors 

The smoke detectors are connected to the 

KSUG and are then operated by the KSUA as 

detector groups, which in turn control the 

dampers. The EXT input is logically 

connected to detector input 1. This means the 

EXT input can be used for a heat detector, for 

example, or an external central fire alarm 

system that can be configured to be part of a 

detector group.  

When you perform a reset on the KSUA all 

detectors are opened for 5 seconds to reset 

them. 

Malfunctions 

If a communication error occurs, the KSUG 

will take over and close the dampers after 15 

seconds. 

Other errors are forwarded to the KSUA for 

central processing. 

LEDs 

Every time a correct message is received, the 

Operation LED switches on or off in order to 

indicate that communication with the master is 

working correctly. The Error LED lights up if 

communication stops. Other LEDs work in the 

same way as in stand-alone mode. 

Buttons 

No function in network mode. 

Stand-alone mode 

(Jumper H must be ON) 

 

Jumpers H and 4 are ON (stand-alone 

mode,RFT MANF VD24 actuator with only 

damper 1 in use) 

Summary of Contents for KSUG

Page 1: ...with BR24 F ST General Slave unit for KSUA RF technologies MANF VD24 or MANF VM24 actuator Belimo BR24 F ST actuator with BSIA24 Can be used as a stand alone unit Two dampers Two detector inputs Built...

Page 2: ...ycle Definitions Ventilation dampers Dampers that are closed by a spring Evacuation dampers Dampers that are opened by a spring Day mode Ventilation dampers open and evacuation dampers closed Night mo...

Page 3: ...umper F H Stand alone mode Network mode Choice of damper actuator Jumper F and G selects the actuator type to be used If jumper F is ON Belimo BSIA24 and BR24 F ST If jumper G is on RFT MANF VM24 type...

Page 4: ...mper is closed Various jumper settings can be used to prevent fan locking Jumper On Off 2 Do not stop in night mode Stop in night mode 16 Do not stop for test Stop for test F No fan delay 30 s delay S...

Page 5: ...ons be switched Is that the case terminal 4 and 5 in the KSUG must be switched Be aware of Jumper 8 F and G for selection of actuator type in stand alone or network mode Shown without power 13 14 is c...

Page 6: ...t jumper F must be ON and 8 OFF in stand alone mode In network mode jumper F must be ON and G OFF Smoke detector inputs The two smoke detector inputs are designed for a loop resistance of 2200 ohm ter...

Page 7: ...within the time specified for the particular actuator The actuator contacts are correctly closed with the dampers in the off position The dampers go to normal position within the time specified for th...

Page 8: ...MP1 and jumper 4 ON That the dampers open and that the green LED is normal Carry out a manual function test and check that the dampers operate within 2 seconds if the MANF VD24 is used The red LED lig...

Page 9: ...must be sent to a collection point that recycles electrical and electronic equipment By making sure this product is correctly processed you will help to prevent the negative impact on the environment...

Reviews: