Operating instructions
SUM ALARM
ERROR
FIRE ALARM
OPERATION
NO
RM
A
L
RESET / TEST
(Press and hold 5sec
for damper test)
DAMPER
STATUS
230V 50Hz 20VA
Status Flash
NO
RM
A
L
O
FF
O
FF
1
2
FAN ON
KSUG
ON Control AB
Gånghester, Sweden.
Tel. +46 33 25 65 70
DETECTOR
SERVICE DET.
TEST CYCLE
Control Panel
Detector failure
Detector needs cleaning
Damper error at test cycle
Indicators and buttons
A. OPERATION
Green LED showing that the unit is receiving
power and indicating day/night mode.
Constant = day mode. Flashing = night mode.
B. ERROR
This LED uses three different flashing
sequences to indicate three different alarms.
•
Constant if the detector loop is broken.
•
Alternating short and long flashes to
indicate a service alarm (dirty smoke
detector). The indication is delayed by one
hour to prevent false alarms. When the
alarm is reset, the delay is deactivated to
make it possible to confirm immediately
that the alarm has been cleared.
•
Rapid flashes if the 48-hour test fails. The
following situations are tested.
•
Both dampers go to off position within
the time specified for the particular
actuator.
•
The actuator contacts are correctly
closed with the dampers in the off
position.
•
The dampers go to normal position
within the time specified for the
particular actuator.
•
The actuator contacts are closed with
the damper in the normal position.
C. FIRE ALARM
The same LED covers both smoke detector
loops. If the LED is red, a detector has been
triggered. The associated relay is closed.
D. SUM ALARM
The sum alarm is indicated by the red LED
and the associated relay output is closed when
the following events occur:
•
Smoke detector 1 or 2 triggered.
•
EXT input activated. (Jumper 1=off)
•
Break in any of the detector loops.
•
Error during function test.
•
Service alarm in any of the detector loops.
•
Damper in incorrect position during normal
operation.
•
Connection error.
E. FAN ON
Fan control is indicated with an LED that
lights up when the relay is closed.
F. RESET / Test
Button to reset the entire alarm. While the
button is pressed, the detector outputs are
disconnected to allow any triggered smoke
detectors to be reset.
If you keep the button pressed for at least 5
seconds, the function test starts when you
release the button. After five seconds, the
Operation and Alarm LEDs stop alternating
A
B
C
E
G
H
F
D