Operating instructions 

 

SUM ALARM

ERROR

FIRE ALARM

OPERATION

NO

RM

A

L

RESET / TEST

(Press and hold 5sec

for damper test)

DAMPER

STATUS

230V 50Hz 20VA

Status Flash

NO

RM

A

L

O

FF

O

FF

1

2

FAN ON

KSUG

ON Control AB

Gånghester, Sweden.

Tel. +46 33 25 65 70

DETECTOR

SERVICE DET.

TEST CYCLE

Control Panel

Detector failure

Detector needs cleaning

Damper error at test cycle

 

 

 

Indicators and buttons 

 

A.  OPERATION 

Green LED showing that the unit is receiving 

power and indicating day/night mode. 

Constant = day mode. Flashing = night mode. 

B. ERROR 

This LED uses three different flashing 

sequences to indicate three different alarms. 

 

Constant if the detector loop is broken. 

 

Alternating short and long flashes to 

indicate a service alarm (dirty smoke 

detector). The indication is delayed by one 

hour to prevent false alarms. When the 

alarm is reset, the delay is deactivated to 

make it possible to confirm immediately 

that the alarm has been cleared. 

 

Rapid flashes if the 48-hour test fails. The 

following situations are tested. 

 

Both dampers go to off position within 

the time specified for the particular 

actuator. 

 

The actuator contacts are correctly 

closed with the dampers in the off 

position. 

 

The dampers go to normal position 

within the time specified for the 

particular actuator. 

 

The actuator contacts are closed with 

the damper in the normal position. 

C. FIRE ALARM 

The same LED covers both smoke detector 

loops. If the LED is red, a detector has been 

triggered. The associated relay is closed. 

D. SUM ALARM 

The sum alarm is indicated by the red LED 

and the associated relay output is closed when 

the following events occur: 

 

Smoke detector 1 or 2 triggered. 

 

EXT input activated. (Jumper 1=off) 

 

Break in any of the detector loops. 

 

Error during function test. 

 

Service alarm in any of the detector loops. 

 

Damper in incorrect position during normal 

operation. 

 

Connection error. 

E. FAN ON 

Fan control is indicated with an LED that 

lights up when the relay is closed. 

F. RESET / Test 

Button to reset the entire alarm. While the 

button is pressed, the detector outputs are 

disconnected to allow any triggered smoke 

detectors to be reset. 

 

If you keep the button pressed for at least 5 

seconds, the function test starts when you 

release the button. After five seconds, the 

Operation and Alarm LEDs stop alternating 

A

 

B

 

C

 

E

 

G

 

H

 

F

 

D

 

Summary of Contents for KSUG

Page 1: ...with BR24 F ST General Slave unit for KSUA RF technologies MANF VD24 or MANF VM24 actuator Belimo BR24 F ST actuator with BSIA24 Can be used as a stand alone unit Two dampers Two detector inputs Built...

Page 2: ...ycle Definitions Ventilation dampers Dampers that are closed by a spring Evacuation dampers Dampers that are opened by a spring Day mode Ventilation dampers open and evacuation dampers closed Night mo...

Page 3: ...umper F H Stand alone mode Network mode Choice of damper actuator Jumper F and G selects the actuator type to be used If jumper F is ON Belimo BSIA24 and BR24 F ST If jumper G is on RFT MANF VM24 type...

Page 4: ...mper is closed Various jumper settings can be used to prevent fan locking Jumper On Off 2 Do not stop in night mode Stop in night mode 16 Do not stop for test Stop for test F No fan delay 30 s delay S...

Page 5: ...ons be switched Is that the case terminal 4 and 5 in the KSUG must be switched Be aware of Jumper 8 F and G for selection of actuator type in stand alone or network mode Shown without power 13 14 is c...

Page 6: ...t jumper F must be ON and 8 OFF in stand alone mode In network mode jumper F must be ON and G OFF Smoke detector inputs The two smoke detector inputs are designed for a loop resistance of 2200 ohm ter...

Page 7: ...within the time specified for the particular actuator The actuator contacts are correctly closed with the dampers in the off position The dampers go to normal position within the time specified for th...

Page 8: ...MP1 and jumper 4 ON That the dampers open and that the green LED is normal Carry out a manual function test and check that the dampers operate within 2 seconds if the MANF VD24 is used The red LED lig...

Page 9: ...must be sent to a collection point that recycles electrical and electronic equipment By making sure this product is correctly processed you will help to prevent the negative impact on the environment...

Reviews: