Summary of Contents for KSUG

Page 1: ...with BR24 F ST General Slave unit for KSUA RF technologies MANF VD24 or MANF VM24 actuator Belimo BR24 F ST actuator with BSIA24 Can be used as a stand alone unit Two dampers Two detector inputs Built...

Page 2: ...ycle Definitions Ventilation dampers Dampers that are closed by a spring Evacuation dampers Dampers that are opened by a spring Day mode Ventilation dampers open and evacuation dampers closed Night mo...

Page 3: ...umper F H Stand alone mode Network mode Choice of damper actuator Jumper F and G selects the actuator type to be used If jumper F is ON Belimo BSIA24 and BR24 F ST If jumper G is on RFT MANF VM24 type...

Page 4: ...mper is closed Various jumper settings can be used to prevent fan locking Jumper On Off 2 Do not stop in night mode Stop in night mode 16 Do not stop for test Stop for test F No fan delay 30 s delay S...

Page 5: ...ons be switched Is that the case terminal 4 and 5 in the KSUG must be switched Be aware of Jumper 8 F and G for selection of actuator type in stand alone or network mode Shown without power 13 14 is c...

Page 6: ...t jumper F must be ON and 8 OFF in stand alone mode In network mode jumper F must be ON and G OFF Smoke detector inputs The two smoke detector inputs are designed for a loop resistance of 2200 ohm ter...

Page 7: ...within the time specified for the particular actuator The actuator contacts are correctly closed with the dampers in the off position The dampers go to normal position within the time specified for th...

Page 8: ...MP1 and jumper 4 ON That the dampers open and that the green LED is normal Carry out a manual function test and check that the dampers operate within 2 seconds if the MANF VD24 is used The red LED lig...