background image

 

 

2015-01-07 

 

 

Page 8/9 

and the Operation LED lights up instead. (The 

function test is usually initiated by the timer 

every 48 hours) 

F and G. DAMPER STATUS 

The green and red LEDs indicate the normal 

position/alarm position respectively for the 

relevant damper. The normal position is open 

for a ventilation damper and closed for an 

evacuation damper. 

The dampers are numbered 1 and 2. 

 

Troubleshooting 

 

The "

ERROR

" LED lights or flashes.  

 

Look at the pattern of flashing to identify 

the error.  

 

If the LED is constantly lit, there is a break in 

the detector loop. 

Check: 

 

The terminating resistor in the last detector 

of the loop with the problem. It should be 

2200 ohm, 0.6 W. 

 

If the input is not used, a resistor of 2200 

ohm must be installed to replace the 

detectors. 

 

Break in cable 

 

Loose contact in the detector bases. 

 

Check the connections to the detectors. 

 

Polarity! 

 

Alternating short and long flashes to indicate a 

service alarm (dirty smoke detector). 

Check: 

 

For dirt on one or more detectors. Indicated 

by a yellow LED on the affected detector if 

the detector has a service alarm function. 

Vacuum-clean or, in the worst case, replace 

the detector head. 

 

Rapid flashes if the 48-hour test fails.

 

Check: 

 

That the right number of dampers are 

connected for the selected mode. If only 

one damper is used, it must be connected to 

DMP1 and jumper 4=ON 

 

That the dampers open and that the green 

LED is normal. 

 

Carry out a manual function test and check 

that the dampers operate within 2 seconds 

if the MANF-VD24 is used. The red LED 

lights up. The dampers must then return to 

the normal position within 200 seconds and 

the green LED lights up.  

 

That the dampers are correctly connected. 

Correct actuator type is selected. Pay 

particular attention to the connection to 

terminal 1. 

 

The "

FIRE ALARM

" LED lights up

.  

Check: 

 

That the EXT input is jumpered or closed 

by an external control unit. 

 

For a short-circuit in one of the detector 

loops. 

 

An alarm from a detector is indicated with 

an LED on the detector. 

 

The "

SUM ALARM

" LED lights up

.

 

Check: 

 

For other alarms indicated by the LEDs. 

 

That no damper has operated incorrectly. 

 

That the dampers are correctly connected. 

 

The dampers do not open. 

Check: 

 

That there are no other alarms on the front 

panel. 

 

That the damper motor is connected 

correctly. 

 

A manual reset is required after an automatic 

function test. 

The "fan lock" output has probably been 

connected to the wrong input in the ventilation 

system, which has locked itself as a result. 

 

A manual reset is required after night mode.

 

Requires a night mode signal from ventilation 

system to the KSUG. 

Locking may occur if night mode is indicated 

by the KSUG, which then sends a stop signal 

to the system via the fan lock. This locking 

may be bypassed by setting jumper 2. The fans 

are still locked if a smoke detector is triggered 

and during the function test. 

Summary of Contents for KSUG

Page 1: ...with BR24 F ST General Slave unit for KSUA RF technologies MANF VD24 or MANF VM24 actuator Belimo BR24 F ST actuator with BSIA24 Can be used as a stand alone unit Two dampers Two detector inputs Built...

Page 2: ...ycle Definitions Ventilation dampers Dampers that are closed by a spring Evacuation dampers Dampers that are opened by a spring Day mode Ventilation dampers open and evacuation dampers closed Night mo...

Page 3: ...umper F H Stand alone mode Network mode Choice of damper actuator Jumper F and G selects the actuator type to be used If jumper F is ON Belimo BSIA24 and BR24 F ST If jumper G is on RFT MANF VM24 type...

Page 4: ...mper is closed Various jumper settings can be used to prevent fan locking Jumper On Off 2 Do not stop in night mode Stop in night mode 16 Do not stop for test Stop for test F No fan delay 30 s delay S...

Page 5: ...ons be switched Is that the case terminal 4 and 5 in the KSUG must be switched Be aware of Jumper 8 F and G for selection of actuator type in stand alone or network mode Shown without power 13 14 is c...

Page 6: ...t jumper F must be ON and 8 OFF in stand alone mode In network mode jumper F must be ON and G OFF Smoke detector inputs The two smoke detector inputs are designed for a loop resistance of 2200 ohm ter...

Page 7: ...within the time specified for the particular actuator The actuator contacts are correctly closed with the dampers in the off position The dampers go to normal position within the time specified for th...

Page 8: ...MP1 and jumper 4 ON That the dampers open and that the green LED is normal Carry out a manual function test and check that the dampers operate within 2 seconds if the MANF VD24 is used The red LED lig...

Page 9: ...must be sent to a collection point that recycles electrical and electronic equipment By making sure this product is correctly processed you will help to prevent the negative impact on the environment...

Reviews: