Section 7
Host Communications Specifications
209
RFID System
User's Manual
(Modbus TCP)
GET COMMUNICATION DIAGNOSTIC SETTING
This query gets the communication diagnostic setting. The communications diagnostic information are
cleared after the Reader/Writer is rebooted.
Query Format
Response Format
Normal Response
Error Response
Execution Example
When Communication Diagnostic Is Enabled
TX: 000000000006FF03B3000001
RX: 000000000005FF03020001
Parameter
Description
Register address
The register address (B300 hex) that specifies setting communication diagnostic
Word count
The number of words in the communication diagnostic setting to read (0001 hex)
Parameter
Description
Byte count
The number of bytes in the communication diagnostic setting that was read (02 hex)
Communication
diagnostic setting
Contains the communication diagnostic setting that was read in 4-digits hexadecimal.
Disabled: 0000 hex (default), Enabled: 0001 hex
Parameter
Description
Exception code
For details, refer to
in this section.
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Transaction
identifier
Protocol identifier
Field length
Unit
identifier
Function code
Register address
Word count
X
X
0000 hex
0006 hex
FF hex
03 hex
B300 hex
0001 hex
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte-8
Byte-9
Byte-10
Transaction
identifier
Protocol identifier
Field length
Unit
identifier
Function code
Byte count
Communication
diagnostic setting
X
X
0000 hex
0005 hex
FF hex
03 hex
02 hex
2 bytes
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Transaction
identifier
Protocol identifier
Field length
Unit
identifier
Function
code
Exception
code
X
X
0000 hex
0003 hex
FF hex
83 hex
1 byte