RFID System
User's Manual
(Modbus TCP)
Section 7
Host Communications Specifications
GET WEB COMMUNICATIONS CONDITIONS
This query reads the WEB information that is set in the Reader/Writer.
Query Format
Response Format
Normal Response
Error Response
Execution Example
Reading the WEB Communications Conditions When the Web Port Is 7090(1BB2 hex)
TX: 000000000006FF03BA000001
RX: 000000000005FF03021BB2
Parameter
Description
Register address
The register address (B800 hex) that specifies the WEB communications conditions.
Word count
The number of words in the WEB communications conditions information to read
(0001 hex)
Parameter
Description
Byte count
The number of bytes in the WEB communications conditions that was read (02 hex)
WEB communications conditions
Contains the Web Port that was read in 4-digits hexadecimal.
Example: 1BB2 hex (7090)
Parameter
Description
Exception code
For details, refer to
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Transaction
identifier
Protocol identifier
Field length
Unit
identifier
Function code
Register address
Word count
X
X
0000 hex
0006 hex
FF hex
03 hex
BA00 hex
0001 hex
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Transaction
identifier
Protocol
identifier
Field length
Unit
identifier
Function code
Byte
count
WEB communications
conditions
X
X
0000 hex
0005 hex
FF hex
03 hex
02 hex
2 bytes
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Transaction
identifier
Protocol identifier
Field length
Unit
identifier
Function
code
Exception
code
X
X
0000 hex
0003 hex
FF hex
83 hex
1 byte