3-5
Section
Wiring
19
flows into the ID Controller upon Power application. Take appropriate measures
against the inrush current.
Use a power cable 2 mm
2
diameter minimum to prevent voltage drops. The use
of twisted pair cables is recommended.
To improve noise immunity, ground at less than 100
Ω
. For a ground cable, use a
cable of 2 mm
2
diameter minimum (green cable), and keep the cable length to
within 20 m.
Recommended Power Supply (Small, DIN Rail Type) <OMRON>
Model
Output
Input voltage
S82K-0124
24 VDC, 0.6 A
100 VAC
S82K-2124
24 VDC, 0.6 A
200 VAC
Note Although the rated power dissipation of the ID Controller is 24 VDC, 0.3 A (7.2
W), take into consideration the power supply ratings taking the inrush current
into the ID Controller. Use a power supply of 24 VDC, 0.6 A minimum.
Input and Output lines
RESET Signal Input
To ERROR output
RESET input
24 VDC
24 VDC
+
+
Make sure that the input voltage of the RESET signal does not exceed the maxi-
mum voltage (26.4 V). If this is exceeded, the ID Controller may malfunction.
To improve the noise immunity, separate the wiring of the input lines from
high-tension equipment or power lines.
ERROR Signal Output
The maximum switching capacity of the output terminals is 24 VDC (
+10%
/
–15%
),
100 mA. If a voltage or load that exceeds the maximum switching capacity is
used, the ID Controller may malfunction. Use of an auxiliary relay (24 VDC, 100
mA max.) in the output circuit is recommended.