Standard Models
Appendix A
434
C200H Standard I/O Units
Name
Specifications
Model number
Input Units
AC Input Unit
8 pts
100 to 120 VAC
C200H-IA121
16 pts
100 to 120 VAC
C200H-IA122/122V
8 pts
200 to 240 VAC
C200H-IA221
16 pts
200 to 240 VAC
C200H-IA222/222V
DC Input Unit
8 pts
No-voltage contact; NPN
C200H-ID001
8 pts
No-voltage contact; PNP
C200H-ID002
8 pts
12 to 24 VDC
C200H-ID211
16 pts
24 VDC
C200H-ID212
AC/DC Input Unit
8 pts
12 to 24 VAC/DC
C200H-IM211
16 pts
24 VAC/DC
C200H-IM212
Interrupt Input Unit
1
8 pts
12 to 24 VDC
C200HS-INT01
Output Units
Relay Output Unit
8 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC221
12 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC222
16 pts
2 A, 250 VAC/24 VAC (For resistive loads)
C200H-OC225
2, 3
5 pts
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
C200H-OC223
8 pts
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
C200H-OC224
12 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC222V
16 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC226
8 pts
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
C200H-OC224V
Triac Output Unit
8 pts
1 A, 120 VAC
C200H-OA121-E
8 pts
1.2 A, 120 VAC
C200H-OA122-E
8 pts
1 A, 200 VAC
C200H-OA221
12 pts
0.3 A, 250 VAC
C200H-OA222V
12 pts
0.5 A, 250 VAC
C200H-OA224
Transistor Output
U i
8 pts
1 A, 12 to 48 VDC
C200H-OD411
p
Unit
12 pts
0.3 A, 24 VDC
C200H-OD211
16 pts
0.3 A, 24 VDC
C200H-OD212
2
8 pts
2.1 A, 24 VDC
C200H-OD213
8 pts
0.8 A, 24 VDC; source type (PNP); with load
short protection
C200H-OD214
8 pts
5 to 24 VDC; source type (PNP)
C200H-OD216
12 pts
5 to 24 VDC; source type (PNP)
C200H-OD217
16 pts
1.0 A, 24 VDC; source type (PNP); with load
short protection
C200H-OD21A
Analog Timer Unit
4 timers
0.1 to 1 s/1 to 10 s/10 to 60 s/1 min to 10 min
(switchable)
C200H-TM001
Variable Resistor
Connector
Connector w/lead wire (2 m) for 1 external resistor
C4K-CN223
Standard B7A Interface Units
16 input pts
Connects to B7A Link Terminals.
C200H-B7AI1
16 output pts
C200H-B7AO1
Note
1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Inter-
rupt Input Unit will be treated as an ordinary 8-point Input Unit. Moreover, Interrupt Input Units cannot be used on
Slave Racks. In addition, Interrupt Input Units require that a version 2 (i.e., model numbers with a “-V2” suffix) Back-
plane be used at the CPU Rack. If an earlier version Backplane is mounted, the interrupt function cannot be used.
2. Transistor Output Unit C200H-OD212 and Contact Output Unit C200H-OC225 must be mounted to either a C200H-
BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2, or C200H-BC101-V1/V2 Backplane.
3. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.