![background image](http://html1.mh-extra.com/html/omron/sysmac-c200hs/sysmac-c200hs_operation-manual_742436037.webp)
26
3-1
Introduction
Details, including the name, size, and range of each area are summarized in the
following table. Data and memory areas are normally referred to by their acro-
nyms, e.g., the IR Area, the SR Area, etc.
Area
Size
Range
Comments
I/O Area
480 bits
IR 000 to IR 029
I/O words are allocated to the CPU Rack and
Expansion I/O Racks by slot position.
1
Group-2 High-density
I/O Unit and B7A
Interface Unit Area
320 bits
IR 030 to IR 049
Allocated to Group-2 High-density I/O Units and
to Group-2 B7A Interface Units 0 to 9
1
SYSMAC BUS Area
800 bits
IR 050 to IR 099
Allocated to Remote I/O Slave Racks 0 to 4.
1
Special I/O Unit Area
1,600 bits
IR 100 to IR 199
Allocated to Special I/O Units 0 to 9.
1
Optical I/O Unit and I/O
Terminal Area
512 bits
IR 200 to IR 231
Allocated to Optical I/O Units and I/O
Terminals.
1
Work Area 1
64 bits
IR 232 to IR 235
For use as work bits in the program.
Special Relay Area 1
312 bits
SR 23600 to SR
25507
Contains system clocks, flags, control bits, and
status information.
Special Relay Area 2
704 bits
SR 256 to SR 299
(298 to 299 reserved
by system)
Contains flags, control bits, and status informa-
tion.
Macro Area
64 bits
SR 290 to SR 293
Inputs
64 bits
SR 294 to SR 297
Outputs
Work Area 2
3,392 bits
IR 300 to IR 511
For use as work bits in the program.
Temporary Relay Area
8 bits
TR 00 to TR 07
Used to temporarily store and retrieve execution
conditions when programming certain types of
branching ladder diagrams.
Holding Relay Area
1,600 bits
HR 00 to HR 99
Used to store data and to retain the data values
when the power to the PC is turned off.
Auxiliary Relay Area
448 buts
AR 00 to AR 27
Contains flags and bits for special functions. Re-
tains status during power failure.
Link Relay Area
1,024 bits
LR 00 to LR 63
Used for data links in the PC Link System.
1
Timer/Counter Area
512 counters/
timers
TC 000 to TC 511
Used to define timers and counters, and to
access completion flags, PV, and SV.
Interval timers 0 through 2 and high-speed
counters 0 through 2 provided in separate area.
TIM 000 through TIM 015 can be refreshed via
interrupt processing as high-speed timers.
Data Memory Area
6,144 words
DM 0000 to DM 6143
Read/Write
y
1,000 words
DM 0000 to DM 0999
Normal DM.
1,000 words
DM 1000 to DM 1999
Special I/O Unit Area
2
4,000 words
DM 2000 to DM 5999
Normal DM.
31 words
DM 6000 to DM 6030
History Log
(44 words)
DM 6100 to DM 6143
Link test area (reserved)
Fixed DM Area
512 words
DM 6144 to DM 6599
Fixed DM Area (read only)
56 words
DM 6600 to DM 6655
PC Setup
Expansion DM Area
3,000 words max.
DM 7000 to DM 9999
Read only
Note
1. These can be used as work words and bits when not used for their allocated
purposes.
2. The PC Setup can be set to use DM 7000 through DM 7999 as the Special
I/O Area.
Introduction