Parameters
Program (Response)
The program is read from the entire program area.
Note To stop this operation in progress, execute the ABORT (XZ) command.
11-3-31 PROGRAM WRITE –– WP
Writes to the PC user’s program area the machine language (object code) pro-
gram transmitted from the host computer. The contents are written as a block,
from the beginning.
Command Format
@
W
P
x 10
0
x 10
1
x 16
1
x 16
0
↵
:
Node no.
Header
code
1 byte
Program (Up to maximum memory size)
Terminator
FCS
Response Format
@
W
P
x 10
0
x 10
1
x 16
1
x 16
0
↵
:
Node no.
Header
code
End code
Terminator
FCS
Parameters
Program ((Command)
Program data up to the maximum memory size.
11-3-32 I/O TABLE GENERATE –– MI
Corrects the registered I/O table to match the actual I/O table.
Command Format
@
M
I
x 10
0
x 10
1
↵
:
Node no.
Header
code
Terminator
FCS
Response Format
@
M
I
x 10
0
x 10
1
x 16
1
x 16
0
↵
:
Node no.
Header
code
End code
Terminator
FCS
11-3-33 COMPOUND COMMAND –– QQ
Registers at the PC all of the bits, words, and timers/counters that are to be read,
and reads the status of all of them as a batch.
Registering Read Information
Register the information on all of the bits, words, and timers/counters that are to
be read.
Host Link Commands