50
Word(s)
Function
Bit(s)
19
00 to 07
Hours: 00 to 23 (24-hour system)
08 to 15
Day of Month: 01 to 31 (adjusted by month and for leap year)
20
00 to 07
Month: 1 to 12
08 to 15
Year: 00 to 99 (Rightmost two digits of year)
21
00 to 07
Day of Week: 00 to 06 (00: Sunday; 01: Monday; 02: Tuesday; 03: Wednesday; 04:
Thursday; 05: Friday; 06: Saturday)
08 to 12
Not used.
13
30-second Compensation Bit
14
Clock Stop Bit
15
Clock Set Bit
22
00 to 15
Keyboard Mapping
23
00 to 15
Power Off Counter (BCD)
24
00
SYSMAC LINK – RS-232C Peripheral Device Flag
01
SYSMAC LINK – Port A Peripheral Device Flag
02
SYSMAC LINK – Port B Peripheral Device Flag
03
SYSMAC LINK – Peripheral Device Initialization BIt
04
Not used.
05
Cycle Time Flag
06
SYSMAC LINK System Network Parameter Flag for operating level 1
07
SYSMAC LINK System Network Parameter Flag for operating level 0
08
SYSMAC LINK/SYSMAC NET Link Unit Level 1 Mounted Flag
09
SYSMAC LINK/SYSMAC NET Link Unit Level 0 Mounted Flag
10
Not used.
11
PC Link Unit Level 1 Mounted Flag
12
PC Link Unit Level 0 / Single Level Mounted Flag
13
Rack-mounting Host Link Unit Level 1 Mounted Flag
14
Rack-mounting Host Link Unit Level 0 Mounted Flag
15
CPU Unit-mounting Device Mounted Flag
25
00 to 07
Password for access to the Online Edit Disable Bit
(The Online Edit Disable Bit is valid when this byte contains 5A.)
08
FPD(––) Trigger Bit
09
Online Edit Disable Bit
10
Online Edit Standby Flag
11
Not used.
12
Trace End Flag
13
Tracing Flag
14
Trace Trigger Bit (writeable)
15
Trace Start Bit (writeable)
26
00 to 15
Maximum Cycle Time (0.1 ms)
27
00 to 15
Present Cycle Time (0.1 ms)
3-5-1 Restarting Special I/O Units
AR bits 0100 to AR 0109 correspond to the unit numbers of Special I/O Units 0 to
9. To restart Special I/O Units (including PC Link Units) turn the corresponding
bit ON and OFF (or turn power ON and OFF). Do not access data refreshed for
Special I/O Units during restart processing (see SR 27400 to SR 27409 on page
37).
Note
Bits SR 28100 to SR 28115 also act as Restart Bits for Special I/O Units 0 to F
.
AR (Auxiliary Relay) Area
Section 3-5
Summary of Contents for SYSMAC C200HE
Page 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Page 2: ......
Page 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Page 6: ...vi ...
Page 10: ......
Page 12: ......
Page 380: ......
Page 410: ......
Page 438: ......
Page 464: ......
Page 474: ......
Page 522: ......
Page 538: ......
Page 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 554: ......
Page 560: ......
Page 584: ......
Page 585: ......
Page 586: ...W303 E1 09 ...