267
Note
1. The actual integral and derivative times are calculated using the values set
in C+2 and C+3 and the time unit set in C+6.
2. Setting the 2-PID parameter (
α
) to 000 yields 0.65, the normal value.
3. The only CQM1 model that can use PID(––) is the CQM1-CPU4
-EV1.
Performance Specifications
Item
Specifications
PID calculation method
---
Target value filter-type, two degrees of freedom (forward/reverse
operation)
Number of PID control loops
---
No limit (1 loop per instruction)
Sampling period
t
0.01 to 102.3 s (See note.)
PID constants
Proportional band
P
0.1 to 999.9%
Integral constant
Tik
1 to 8191, 9999 (No integral operation for sampling period multiple or
9999.)
Derivative constant
Tdk
0 to 8191 (No derivative operation for sampling period multiple.)
Set value
SV
0 to 65,535 (Valid up to the maximum value of the input range.)
Measured value
PV
0 to 65,535 (Valid up to the maximum value of the input range.)
Operation output amount
MV
0 to 65,535 (Valid up to the maximum value of the output range.)
Note
For the C200HS and the CQM1-CPU4
-EV1, the sampling period is 0.1 to
102.3 s.
Special Math Instructions
Section 5-21
Summary of Contents for SYSMAC C200HE
Page 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Page 2: ......
Page 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Page 6: ...vi ...
Page 10: ......
Page 12: ......
Page 380: ......
Page 410: ......
Page 438: ......
Page 464: ......
Page 474: ......
Page 522: ......
Page 538: ......
Page 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 554: ......
Page 560: ......
Page 584: ......
Page 585: ......
Page 586: ...W303 E1 09 ...