329
RECV(98) receives “m” words beginning with S (the beginning word for data
transmission at the destination node, M) to the words from D (the beginning word
for data reception at the source node) onwards.
Direct/Indirect
0: Direct; 1: Indirect
S: Destination node beginning send word
D: Source node beginning receive word
C: Source node first control data word
Destination node M
Source node
C + 2
@RECV(98)
S
D
C
C
“m” number of send words
0000 to 03DE (Hex): 0 to 990 words
C + 1 1
0: Operating level 1
1: Operating level 0
Always “1” for Controller Link Networks
0: Response required
1: Response not required
Destination (transmission source) node address (M)
00 to 20 (Hex): 0 to 32
The range of node addresses will vary for networks
other than Controller Link Networks.
0: Source network address not specified (local network)
1: Source network address specified.
Response monitor time
00 (Hex):
2 s (for 2 Mbps)
4 s (for 1 Mbps)
8s (for 500 Kbps)
01 to FE (Hex): 0.1 to 25.4 s (unit: 0.1 s)
FF (Hex):
No response monitoring
Destination (transmission source) unit address
00 (Hex):
PC’s CPU Unit
01 (Hex):
Computer (user program)
10 to 1F (Hex): Unit nos. 0 to 15
FE (Hex):
Unit connected to network
C + 3
0
0
Destination network address
00 (Hex):
Local network
01 to 7F (Hex): 1 to 127
This setting is enabled only when “Destination network address specified” is set in word C.
When specifying the destination network address, set all the nodes in the routing tables. For
details on the routing tables, refer to the section on network interconnections in the
Controller
Link Unit Operation Manual (W309)
.
1514
0
1514131211
8 7
8 7
0
15
0
15
0
Direct/Indirect
Number of retries
0 to F (Hex): 0 to 15 retries
“m” num-
ber of
send
words
D
15
0
15
0
L
m
S
L
Note
1. When communicating in the same network with CV-series PCs manufac-
tured prior to April 1996, the local network address cannot be set to “00.” Set
a number other than “00” as the local network address in the routing tables,
and then specify that number.
Controller Link Systems
Network Instructions
Section 5-26
Summary of Contents for SYSMAC C200HE
Page 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Page 2: ......
Page 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Page 6: ...vi ...
Page 10: ......
Page 12: ......
Page 380: ......
Page 410: ......
Page 438: ......
Page 464: ......
Page 474: ......
Page 522: ......
Page 538: ......
Page 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 554: ......
Page 560: ......
Page 584: ......
Page 585: ......
Page 586: ...W303 E1 09 ...