345
The following example illustrates connections for an A7B Thumbwheel Switch.
1
3
5
7
9
11
13
15
COM
0
2
4
6
8
10
12
14
COM
ID212
Input Unit
Switch no. 8
1
3
5
7
9
11
13
15
COM
0
2
4
6
8
10
12
14
DC
OD212
1
2
4
8
7
6
5
4
3
2
1
C
Output Unit
A7B
Thumbwheel
Switch
Note
The data read signal is not required in the example.
The inputs must be connected to a DC Input Unit with 8 or more input points and
the outputs must be connected from a Transistor Output Unit with 8 or more out-
put points.
Advanced I/O Instructions