328
Control Data
Ethernet Systems
Refer to the
PC Card Unit Operation Manual
for details.
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000
hex
to 03E8
hex)
C+1
Response time limit (0.1 and 25.4
seconds in 0.1 s increments in
2-digit hexadecimal without
decimal point, i.e., 01
hex
to FF
hex
)
Default is 00
hex
(2 seconds)
Bits 08 to 11:
No. of retries (0 to 15 in
hexadecimal,
i.e., 0
hex
to F
hex
)
Bit 12
ON: Direct source
beginning word
designation
OFF: Indirect designation
Bit 13
ON: Response not
returned.
OFF: Response returned.
Bit 14
ON: Operating level 0
OFF: Operating level 1
Bit 15:
Set to 1.
C+2
Source node (0 to 127 in 2-digit
hexadecimal, i.e., 00
hex
to 7F
hex
)*
Bits 08 to 12:
Unit address of source
node. Set to 00
hex
.
Bits 13 to 15: Set to 0.
SYSMAC NET Link Systems
The source port number is always set to 0. Set the network number to 0 to re-
ceive data to a node on the same Subsystem (i.e., network). Refer to the
SYS-
MAC NET Link System Manual
for details.
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000
hex
to 03E8
hex
)
C+1
Network number (0 to 127 in 2-digit
hexadecimal, i.e., 00
hex
to 7F
hex
)
Bit 12
ON: Direct source
beginning word designation
OFF: Indirect designation
Bit 14
ON: Operating level 0
OFF: Operating level 1
Bits 08 to 11, 13 and 15: Set to 0.
C+2
Source node (1 to 126 in 2-digit
hexadecimal, i.e., 01
hex
to 7E
hex
)
Source port
NSB: 00
NSU: 01/02
SYSMAC LINK Systems
Refer to the
SYSMAC LINK System Manual
for details.
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000
hex
to 0100
hex
)
C+1
Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal
without decimal point, i.e., 00
hex
to
FF
hex
)
Note:
The response time will be
2 seconds if the limit is set to 0
hex
.
There will be no time limit if the
time limit is set to FF
hex
.
Bits 08 to 11:
No. of retries (0
to 15 in
hexadecimal,
i.e., 0
hex
to F
hex
)
Bit 12
ON: Direct source
beginning word
designation
OFF: Indirect designation
Bit 13: Set to 0.
Bit 14
ON: Operating level 0
OFF: Operating level 1
Bit 15:
Set to 1.
C+2
Source node (0 to 62 in 2-digit
hexadecimal, i.e., 00
hex
to 3E
hex
)
Set to 0.
Network Instructions
Section 5-26
Summary of Contents for SYSMAC C200HE
Page 1: ...Cat No W303 E1 09 OPERATION MANUAL Programmable Controllers C200HX C200HG C200HE ...
Page 2: ......
Page 3: ...C200HX C200HG C200HE Programmable Controllers Operation Manual Revised August 2004 ...
Page 6: ...vi ...
Page 10: ......
Page 12: ......
Page 380: ......
Page 410: ......
Page 438: ......
Page 464: ......
Page 474: ......
Page 522: ......
Page 538: ......
Page 552: ...534 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 554: ......
Page 560: ......
Page 584: ......
Page 585: ......
Page 586: ...W303 E1 09 ...