67
Appendix B
Sensor Temperature Measurement Ranges
C200H-TC00
j
Thermocouple
8
9
0
1
2
4
3
5
6
7
Set the thermocouple type with the switch on the rear panel.
This switch is factory-set to 2 (K).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input
R
Platinum vs.
platinum
rhodium
13%
S
Platinum
vs.
platinum
rhodium
10%
K (CA)
Chromel vs.
alumel
J/L (IC)
Iron vs.
constantan
T/U (CC)
Copper vs.
constantan
E (CRC)
Chromel vs.
constantan
B
Platinum
rhodium
30% vs.
platinum
rhodium 6%
N
Nichrosil
vs. nisil
Range
°
C 0 to 1,700
0 to 1,700
–200 to
1,300
–100 to
850
–200 to
400
0 to 600
100 to
1,800
0 to 1,300
°
F
0 to 3,000
0 to 3,000
–300 to
2,300
–100 to
1,500
–300 to
700
0 to 1,100
300 to
3,200
0 to 2,300
Switch
setting
0
1
2
3/8
4/9
5
6
7
C200H-TC10
j
Platinum Resistance Thermometer
OFF
ON
Set the platinum resistance thermometer type with the switch on the rear panel.
This switch is factory-set to OFF (JPt100).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input
JPt100
Pt100
Range
°
C
–99.9 to 450.0
–99.9 to 450.0
°
F
–99.9 to 800.0
–99.9 to 800.0
Switch
setting
OFF
ON
electronic components distributor