65
Appendix A
Specifications
General Specifications
Conforms to the CPU Unit specifications.
Item
C200H-TC00
j
C200H-TC10
j
Connectable temperature
sensor (see note 1)
Thermocouple (R, S, K, J, T, E, B, N, L, U)
Platinum resistance thermometer (JPt100,
Pt100)
Current Transformer detection
current
0.1 to 4.9 A (with a heater burnout detecting current difference of 0.5 A min.)
Indication accuracy:
±
5% FS
±
1 digit max.
No. of input points (loops)
Two points (two loops, each of which consists of a temperature sensor and a CT)
Temperature control mode
PID, ON/OFF (selectable with a switch on the rear panel)
(PID control with feed-forward circuitry with auto-tuning)
Setting/Indication accuracy
(see note 2 and 3)
±
0.5% of set (designated) value or
±
2
°
C
whichever larger
±
1 digit max.
±
0.5% of set (designated) value or
±
1
°
C
whichever larger
±
1 digit max.
Hysteresis
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F) (during ON/OFF control action)
Proportional band
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Integral (reset) time
0 to 9999 s (in units of 1 s)
Derivative (rate) time
0 to 9999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Sampling period
500 ms
Output refresh period
500 ms
Display refresh period
500 ms
Input shift range
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Alarm output setting range
–999
°
to 9,999
°
C/
°
F (in units of 1
°
C/
°
F)
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
No. of banks
8 banks
Internal current consumption
5 VDC, 0.33 A max.
External supply voltage
24 VDC
+10%
/
–15%
, 0.2 A min.
Dimensions (see note 4)
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
Weight
360 g
Note 1. Set with the switch on the rear panel. See
Appendix B Sensor T
emperature Measurement Range for the
measurable temperature range.
2. The set value and designated value coincide with each other.
3. The indication accuracy of thermocouples R and S at a temperature of 200
°
C max., that of thermocou-
ples K and T at a temperature of –100
°
C max, and that of thermocouple U are all
±
4
°
C,
±
1 digit max. The
indication accuracy of thermocouple B at a temperature of 400
°
C or below is not guaranteed.
4. See
Appendix D Dimensions.