58
Timing Chart
23301
23302
23303
23304
23305
23306
23307
1 cycle
(Read data)
Wd 2005
200600
(Read complete)
: Point of Read command execution
: Point where data (1) is read.
: Point where data (2) is read.
1
2
4-3-3 Operation Timing
The following descriptions apply to the C200HX/HG/HE, C200HS, C200H, and
CS1 Series.
Write Operation Timing
ON
OFF
ON
OFF
Approx.
140 ms
Command (Wd n)
Write data (Wd n+1)
Write request
(Wd n+2), bit 00
Data (1)
Data (2)
Data (3)
Data (4)
Write complete
(Wd n+6), bit 08
1, 2, 3...
1. The data is written to the Temperature Control Unit EEPROM when the
Write Request Flag turns ON.
2. The Write Complete Flag turns ON when the data writing operation is com-
pleted. It takes approximately 140 ms to write the data.
3. The Write Complete Flag automatically turns OFF when the Write Request
Flag turns OFF.
Check the Write Complete Flag is ON before turning OFF the Write Request
Flag. If the Write Request Flag is set to OFF before the Write Complete Flag
turns ON the Write Complete Flag will not subsequently turn ON.
Programming
Section 4-3