48
Timing Chart
25315
23201
23202
23203
23204
23205
23206
23207
10200
10608
(1 cycle ON)
1 cycle
(Write request)
(Write complete)
↑
: Point of Write command execution
In addition to the above, IR 23201 will turn ON for one cycle on the rising edge of
SW2-2 (IR 10701). One cycle after IR 23208 turns ON, IR 10200 (write request)
will turn ON.
Example 2: Read with SW2-1 Set for Normal Memory Allocations
Description and Conditions
Example:
The following data is read from the indicated addresses:
Loop 1 PV: DM0000
Loop 1 control output variable: DM0001
Loop 2 heater current: DM0002
This read program is to be executed after writing the data with program
example 1.
Conditions: C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109.
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
Programming
Section 4-3