Word
Input
n+3
Loop 1 PV (see note)
n+4
Loop 2 PV (see note)
n+5
Read data
n+6
0
Write
error
0
0
Write
com-
plete
0
0
0
0
Read
com-
plete
n+7
Loop 1 executed bank
b
Loop 2 executed bank
b
0
0
0
SW data
number
number
2-2
2-1
n+8
Loop 1 status data
0
Sen-
sor
error
CT
over-
flow
0
0
0
0
STOP
0
0
0
Con-
trol
out-
put
AT
HB
AL1
AL2
n+9
Loop 2 status data
0
Sen-
sor
error
CT
over-
flow
0
0
0
0
STOP
0
0
0
Con-
trol
out-
put
AT
HB
AL1
AL2
Note For four-digit BCD and platinum resistance thermometer data, the least
significant digit = 0.1, and the most significant digit (F) = minus (–). For example,
“1000” represents 100.0
°
C for a platinum resistance thermometer.
4-1-2 Memory Contents
SW2-1 Set for Fixed Memory Allocations
(CS1: n=2000+10 x Unit number)
(C200HX/HG/HE, C200HS, C200H: n=100 + 10 x Unit number)
I/O
Address
Data item
Data contents
Word
Bit
Output
n
15 to 00
Loop 1 SP
Sets the Loop 1 and Loop 2 SP (set point) as 4-digit BCD data.
For platinum resistance thermometer data, the least significant
digit is 0 1 Set the most significant digit to F for minus (–)
n+1
15 to 00
Loop 2 SP
digit is 0.1. Set the most significant digit to F for minus (–).
Note These specified values apply to the bank number set with Wd
(n+2) and can only be changed in RAM. (Refer
page
44)
n+2
15 to 12
Loop 1
executed
bank
number
Sets the bank number executed for Loop 1 and Loop 2 as 1-digit
BCD data. Set executed bank numbers from 1 to 8. If the value is
set out of this range, the bank number reverts to the previous
value (default value = 1).
11 to 08
Loop 2
executed
bank
number
a ue (de au
a ue
)
07
---
Not used. Set to 0.
06
Loop 1
STOP
Bit set to 0 during temperature control of Loop 1 and set to 1
when the control stop is executed. This bit will not be available
under the program mode with SW203-5 set to ON (same as the
control stop).
05
---
Not used. Set to 0.
04
Loop 2
STOP
Bit set to 0 during temperature control of Loop 2 and set to 1
when the control stop is executed. This bit will not be available
under the program mode with SW203-5 set to ON (same as the
control stop).
03 to 00
---
Not used. Set each bit to 0.
Memory Allocation
Section 4-1