65
C200H Slaves use a 2-piece connector. When attaching this connector, press
down firmly until you hear it lock into place, and then confirm that the lock
lever is in place. The connectors are wired as shown below.
C200H-RT201
+
+
–
AC input
Voltage switch
Shorted: 100V
Open:
200V
LG
GR
24 VDC output
0.3 A
RUN output
Power supplied at either 100 to 120 VDC
or 200 to 240 VDC
Use enclosed device to short for 100-V
power supply. When using 200-V power
supply, verify that circuit is open.
Connect to independent ground to pre-
vent shock.
Connect to independent ground to reduce
noise interference and prevent shock.
Use to power DC Input Units. Use a sepa-
rate power supply if exceeding 3.0 A. If
3.0 A is exceeded, PC may detect error
and stop operation.
ON in RUN mode. Use for accessing sig-
nals from PC in RUN mode.
Fuse
*
* The LG and GR terminals are
connected internally.
7.3
M3.5
3 max.
Terminals
Use thick cables (1.25 mm
2
min.) to prevent against voltage drops.
M3.5 self-rising terminals screws are used for the terminal block. When wir-
ing to the terminal block, use round crimp terminals with the M3.5 screws. Do
not connect stranded wires directly to the terminal block.
Caution
Tighten the screws on the terminal block of the AC Power Supply Unit to a torque
of 0.8 N
S
m. Loose screws may result in short-circuiting, malfunction, or burning.
C200H Slave Connectors
AC Power Supply Wiring
Precautions
Wiring
Section 5-5