Self-Diagnosis
Section 7-1
Error Before Operation: C500 Masters and Slaves
Programming
Console LEDs
LEDs on Master
LEDs on
Slave
Remote
Terminal LEDs
Cause
Correction
TR/
ERR
TEST
OK
END
RS
CHK
LINE
ERR
TR/
ERR
ERR
POWER
TR/
ERR
CPU WAITING
flash
not lit
lit
not lit lit
not lit
lit
lit
Terminator not set.
Set farthest Unit
from Master as
terminator.
Transmission line
broken or wired
incorrectly.
Correct
transmission line
Slave and Remote
Terminal points
exceed 512.
Reduce total
number of points.
not lit not lit
Power not
supplied to
terminator Slave.
Supply power to
Slave.
lit
not lit
not lit
not
lit
Power not
supplied to
terminator Remote
Terminal.
Supply power to
Remote Terminal.
flash
not lit
flash
not lit lit
not lit
lit
lit
Multiple
terminators set.
Refer to 7-7 Slave
Unit Numbers with
Multiple Termina-
tors.
Set only one
terminator for
each Master.
lit
not lit
not
lit
lit
lit
not lit
lit
lit
Transmission line
shorted.
Correct
transmission line.
CPU WAITING
or
REMOTE I/O
ERR
flash
/lit
not lit
---
not lit lit
not lit
lit
lit
Same unit number
or word set twice
on Slaves.
Correct settings
so same word is
not allocated
twice.
lit
not lit
---
not lit lit
lit
lit
lit
Slave I/O bus
error.
Check Slave, I/O
Units on Slave,
and Slave’s Rack.
REMOTE I/O
ERR
or
VER ERR
not
lit
not lit
not
lit
not lit lit
not lit
lit
lit
CPU Unit error in
Master.
Replace Master.
I/O VER ERR
not
lit
not lit
not
lit
not lit lit
not lit
lit
lit
I/O table not
written or I/O table
inconsistency.
(LEDs will go out
after TR/ERR LED
on Master flashes
and terminator
LEDs are lit for
several seconds.)
Check I/O table on
Programming
Console and
correct if
necessary. If I/O
table verifies,
check all Slaves
not set as
terminators.