S8VS

7

Note:

Refer to page 5 for notes 1 to 11.

Power ratings

240 W

480 W

Item

Type

Standard

Maintenance 

forecast monitor

Total run time 

monitor

Standard

Maintenance 

forecast monitor

Total run time 

monitor

Efficiency

With 100-VAC input

85% typical

89% typical

With 200-VAC input

88% typical

93% typical

Input

Voltage 

*

1

100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC 

*

11)

100 to 240 VAC (allowable range: 85 to 264 VAC)

Frequency 

*

1

50/60 Hz (47 to 63 Hz)

Current

With 100-VAC input

3.8 A max., 2.9 A typical

7.4 A max., 5.8 A typical

With 200-VAC input

2.0 A max., 1.5 A typical

3.9 A max., 2.8 A typical

Power factor

0.9 min.

0.95 min.

Harmonic current regulation

Conforms to EN61000-3-2

Leakage current

With 100-VAC input

0.5 mA max.

With 200-VAC input

1.0 mA max.

Inrush current 

*

2

With 100-VAC input

17.5 A max., 14 A typical

With 200-VAC input

35 A max., 28 A typical

Output

Voltage adjustment range 

*

3

10% to 15% (with V.ADJ)

10% to 15% (with V.ADJ)

Ripple noise voltage (at rated I/O)

140 mV max.

160 mV max.

310 mV max.

Input variation influence

0.5% max. (at 85- to 264-VAC input, 100% load)

Load variation influence 
(rated input voltage)

1.5% max. (with rated input, 0 to 100% load)

Temperature variation influence

0.05%/

°

C max.

Startup time 
(at rated I/O) 

*

2

With 100-VAC input

540 ms typical

510 ms typical

550 ms typical

With 200-VAC input

230 ms typical

510 ms typical

550 ms typical

Output hold time 
(at rated I/O) 

*

2

With 100-VAC input

64 ms typical

46 ms typical

37 ms typical

With 200-VAC input

64 ms typical

46 ms typical

41 ms typical

Additional
functions

Overload protection 

*

2

105% to 160% of rated load current, inverted L voltage drop, 
automatic reset

151% to 165% of rated load current, inverted L voltage drop, 

intermittent, automatic reset

Overvoltage protection 

*

2, 

*

4

Yes

Output voltage indication 

*

5

No

Yes (selectable) 

*

6

No

Yes (selectable) 

*

6

Output current indication 

*

5

No

Yes (selectable) 

*

7

No

Yes (selectable) 

*

7

Peak-hold current indication 

*

5

No

Yes (selectable) 

*

8

No

Yes (selectable) 

*

8

Maintenance forecast monitor indication 

*

5

No

Yes (selectable)

No

Yes (selectable)

No

Maintenance forecast monitor output 

No

Yes (transistor output), 
30 VDC max., 50 mA 
max. 

*

9

No

Yes (transistor 
output), 30 VDC 
max., 50 mA max.

No

Total run time monitor indication 

*

5

No

Yes (selectable)

No

Yes (selectable)

Total run time monitor output 

*

5

No

Yes (transistor output), 
30 VDC max., 50 mA 
max. 

*

9

No

Yes (transistor output), 
30 VDC max., 50 mA 
max. 

*

9

Undervoltage alarm indication 

*

5

No

Yes (selectable)

No

Yes (selectable)

Undervoltage alarm output terminals

No

Yes (transistor output), 30 VDC max., 
50 mA max. 

*

9

No

Yes (transistor output), 30 VDC max., 
50 mA max. 

*

9

Parallel operation

No (However, backup operation is possible. An external diode is required.)

Series operation

Yes for up to 2 Power Supplies (with external diode)

Other

Operating ambient temperature

Refer to the derating curve in . (with no icing or condensation)

Storage temperature

25 to 65

°

C

Operating ambient humidity

25% to 85% (Storage humidity: 25% to 90%)

Dielectric strength

3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detection current: 20 mA) 
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard 240-W and 480-W 
models: 30 mA, detection current for 240-W models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)

Insulation resistance

100 M

Ω

 min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC

Vibration resistance

10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions: 240 W
10 to 150 Hz, 0.35-mm single amplitude (3 G max.) for 80 min each in X, Y, and Z directions: 480 W

Shock resistance

150 m/s

2

, 3 times each in ±X, ±Y, and ±Z directions

Output indicator

Yes (color: green)

EMI

Conducted 
Emissions

Models with indication monitor: Conforms to EN55011 Group1 
Class A and based on FCC Class A, Conforms to EN55011 
Group1 Class B 

*

11

Standard models: Conforms to EN55011 Group1 Class B and 
based on FCC Class A

Conforms to EN55011 Group1 Class A and based on FCC 
Class A
Conforms to EN55011 Group1 Class B 

*

11

Radiated Emissions

Models with indication monitor: Conforms to EN55011 Group1 
Class A, Conforms to EN55011 Group1 Class B 

*

11

Standard models: Conforms to EN55011 Group1 Class B

Conforms to EN55011 Group1 Class A
Conforms to EN55011 Group1 Class B 

*

11

EMS

Conforms to EN61204-3 high severity levels

Approved standards

 *

11

UL 508 (Listing)
CSA C22.2 No.107.1 (cUL)
EN 62477-1
EAC mark, RCM mark, KOSHA S Mark 

*

10

UL 508 (Listing)
UL 60950-1 (Recognition)
UL 62368-1 (Recognition)
CSA C22.2 No.107.1 (cUL)
CSA C22.2 No. 60950-1 (cUR), No. 62368-1 (cUR)
EN 50178 (=VDE 0160), EN 60950-1 (=VDE 0805 Teil 1)
EAC mark, RCM mark

SEMI 

*

11

F47-0706 (200-VAC input)

Weight

1,150 g max.

1,700 g max.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Summary of Contents for S8VS-015 Series

Page 1: ...d Safety Precautions on page 32 Recommended Noise Filter Noise filter S8V NF For more information refer to S8V NF Noise Filter Data Sheet Cat No T212 E1 1 2 3 4 5 6 S8VS 1 Power Ratings 015 15 W 030 3...

Page 2: ...t 30 A 200 VAC S8VS 48024 S8VS 48024 F Power ratings Input voltage Output voltage Output current Alarm output 2 UL Class 2 Output standards Model number screw terminal block Model number screwless ter...

Page 3: ...typical 360 ms typical 380 ms typical 400 ms typical Output hold time at rated I O 2 With 100 VAC input 39 ms typical 27 ms typical 28 ms typical 31 ms typical 22 ms typical 31 ms typical With 200 VAC...

Page 4: ...ypical 33 ms typical With 200 VAC input 158 ms typical 154 ms typical Additional functions Overload protection 2 105 to 160 of rated load current 101 to 110 of rated load current for the S8VS 09024 S...

Page 5: ...o 110 of rated load current for the S8VS 09024 S inverted L voltage drop intermittent automatic reset Overvoltage protection 2 4 Yes Output voltage indication 5 No Yes selectable 6 Output current indi...

Page 6: ...Total run time monitor indication 5 No Yes selectable No Yes selectable Total run time monitor output 5 No Yes transistor output 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9...

Page 7: ...ble No Yes selectable Undervoltage alarm output terminals No Yes transistor output 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9 Parallel operation No However backup operation...

Page 8: ...S8VS 015 15 W Voltage detection circuit Photocoupler Rectifier smoothing circuit AC L INPUT AC N Drive control circuit V V DC output Fuse 4 0 A Undervoltage indicator Overvoltage detection circuit Noi...

Page 9: ...ifier S8VS 06024A 60 W S8VS 06024B 60 W S8VS 06024 60 W AC L INPUT AC N V V DC OUTPUT Fuse 6 3 A Rectifier Voltage detection circuit Photocoupler Rectifier smoothing circuit Noise filter Drive control...

Page 10: ...uit Overvoltage detection circuit Current detection circuit S8VS 09024A 90 W S8VS 09024B 90 W S8VS 09024BE 90 W S8VS 09024A S 90 W S8VS 09024B S 90 W S8VS 09024BES 90 W S8VS 09024 90 W S8VS 09024S 90...

Page 11: ...ing circuit V V DC OUTPUT Alarm DC Low S8VS 12024A 120 W S8VS 12024B 120 W S8VS 12024BE 120 W S8VS 12024 120 W Photocoupler Rectifier smoothing circuit INPUT V V DC OUTPUT AC L AC N Fuse 5 0 A Rectifi...

Page 12: ...peration circuit Alarm DC Low S8VS 18024A 180 W S8VS 18024B 180 W S8VS 18024BE 180 W S8VS 18024 180 W Photocoupler INPUT Rectifier smoothing circuit V V DC OUTPUT Fuse 6 3 A AC L AC N Voltage detectio...

Page 13: ...V V V V DC OUTPUT S8VS 24024A 240 W S8VS 24024B 240 W S8VS 24024BE 240 W S8VS 24024 240 W DC OUTPUT INPUT Inrush current protection circuit Harmonic current suppression circuit Power factor improveme...

Page 14: ...0 W 90 120 180 and 240 W Sinking type 11 12 13 Undervoltage Undervoltage Maintenance forecast time or total run time Maintenance forecast time or total run time Common 90 120 180 and 240 W Sourcing ty...

Page 15: ...al 2 3 DC Output terminals V V Connect the load lines to these terminals 4 Output indicator DC ON Green Lights while a direct current DC output is ON 5 Undervoltage indicator DC LOW Red Lights when a...

Page 16: ...DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 3 6 Main display Red 4 Indicates the measurement or set value 7 Operation indicator Orange 4 V Lights up when the output volt...

Page 17: ...on of total run time monitor Blinks during setup of total run time monitor S8VS 48024B 8 Mode Key 3 Use the Mode Key to change the indicated parameter or reset the peak hold current value 9 Up Key 3 U...

Page 18: ...ced air cooling 3 When using a 480 W model at an input voltage of 95 VAC or less derate the load by at least 80 4 DC Inputs If the input voltage is less than 100 VDC reduce the load given in the above...

Page 19: ...our boost current conditions Time that the boost current flows t1 10 s The boost current Ip Maximum boost current The average output current Iave Rated output current The time ratio of the boost curre...

Page 20: ...t terminal DC LOW Example Outputting an Alarm When the Voltage Output by the S8VS 09024A Drops to the Set Value 19 0 V or Lower Note 1 Operation begins after about three seconds since the AC power is...

Page 21: ...90 W S8VS 09024S 90 W S8VS 12024 120 W S8VS 09024A 90 W S8VS 09024A S 90 W S8VS 12024A 120 W S8VS 09024B 90 W S8VS 09024B S 90 W S8VS 12024B 120 W S8VS 09024BE 90 W S8VS 09024BES 90 W S8VS 12024BE 120...

Page 22: ...Stopper 35 4 S8VS 06024 F 60 W S8VS 06024A F 60 W S8VS 06024B F 60 W Rail Stopper 10 97 3 50 1 1 10 max 110 3 115 3 35 4 115 1 4 5 Sliding 15 max S8VS 09024 F 90 W S8VS 09024S F 90 W S8VS 12024 F 120...

Page 23: ...150 1 127 2 1 122 2 Rail Stopper Rail Stopper 96 3 35 4 115 1 S8VS 48024 F 480 W S8VS 48024A F 480 W S8VS 48024B F 480 W Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com...

Page 24: ...10 M4 spring washer M4 8 pan head screw S8VS Input side Output side 15W S82Y VS C2P S 30W S82Y VS C2P S 60W S82Y VS C3P S82Y VS C2P M 90W S82Y VS C3P S82Y VS C2P M 120W S82Y VS C3P S82Y VS C2P M 180W...

Page 25: ...1 Left side mounting Right side mounting t 2 0 89 78 55 0 1 47 5 4 5 dia 0 1 80 60 0 1 Left side mounting Right side mounting also possible 60 0 1 55 0 1 13 80 78 114 4 5 dia 0 1 t 2 0 60 Left side m...

Page 26: ...s recorded and displayed Total run time monitor Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is monitored and displayed Peak h...

Page 27: ...econds Peak hold current will be displayed 2 seconds after it is reset Key Press 3 seconds or more Operation Mode Output current Peak hold current Maintenance forecast monitor Undervoltage alarm Under...

Page 28: ...the set value of the corresponding point The set value must return to the shipment setting Shipment setting or value set in the setting mode again e02 Memory error of alarm set value of maintenance f...

Page 29: ...forecast output terminal Yrs will turn OFF to indicate the need for maintenance The transistor turns OFF when the maintenance forecast time is reached i e there will be no continuity at the maintenan...

Page 30: ...pped with output 4 The accuracy of the maintenance forecast function may be adversely affected by applications in which the AC input is frequently turned ON OFF Reference Values 15 W to 480 W Models N...

Page 31: ...gher than the value displayed for the total run time Time Chart Setting is possible for the following models only S8VS 09024B S8VS 09024BE S8VS 12024B S8VS 12024BE S8VS 18024B S8VS 18024BE S8VS 24024B...

Page 32: ...pletely A protective earthing terminal stipulated in safety standards is used Electric shock or malfunction may occur if the ground is not connected completely Minor fire may possibly occur Ensure tha...

Page 33: ...cast monitor output Yrs or total run time monitor output kh is correctly functioning by the following procedure 1 Select the operation mode 2 Check that the output Yrs kh is turned ON with continuity...

Page 34: ...egative Outputs The outputs are floating outputs i e the primary circuits and secondary circuits are separated You can therefore make positive and negative outputs by using two Power Supplies You can...

Page 35: ...he load is in overload status or is short circuited Remove wires to load when checking Checking overvoltage or internal protection Turn the power supply OFF once and leave it OFF for at least 3 minute...

Page 36: ...Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Ar...

Page 37: ...ide applicable third party certification documents identifying ratings and limitations of use which apply to the Product This information by itself is not sufficient for a complete determination of th...

Page 38: ...5037 2222 Fax 86 21 5037 2200 Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded fro...

Reviews: