S8T-DCBU-01
S8T-DCBU-01
S8T-BUS03
Connect the S8T-BUS03 Connector to the DC line only (AC line
not connected) for use.
The S8T-BUS03 Bus Line Connector is equipped with a selector
to prevent erroneous connection of Blocks with different output
voltage specifications. Slide the selector to 24 V.
Mounting
Mounting Direction
Use standard mounting only. Using any other mounting method
will prevent proper heat dissipation and may result in deterioration
or damage of internal elements.
Stopping Unit
When stopping a connected unit during maintenance, we
recommend first making sure that backup operation is not needed
before turning the battery holder switch and then the AC power line
OFF.
Checking Performances
When having finished connecting equipment to the S8TS-06024
Basic Block and S8T-DCBU-01, we recommend checking that
backup is performed properly by the following procedure.
1.
Turn ON the power of battery holder.
2.
Turn ON the S8TS-06024
AC power line.
3.
Check the operating status described below after 10 seconds
or more.
4.
Turn OFF the S8TS-06024
AC power line.
5.
Check that backup is performed properly by the following
figures.
6.
Turn ON the S8TS-06024
AC power line.
Note:
1.
Check the S8T-DCBU-01 is performed properly after
making sure that no problems will occur as a result of
stopping power to connected loads.
2.
Note that backup operation may not be switched to if
the AC power line is turned OFF for less than 10
seconds at step 3.
Standard mounting
Yes
Face-up mounting
No
Other mounting methods
No
Selector
−
V+V
−
V
+V
−
L N GR
S8T-BUS03
S8TS-06024
S8T-DCBU-01
+
Standard mounting
Face-up mounting
COM
OK
LOW
Relay (BAT LOW)
(6)-(5): ON
Battery status
output relay
4
5
6
LED lit
(DC ON: Green)
Relay (OPN MODE)
(3)-(2): ON
Operation mode
output relay
Indicator
1
2
3
COM
Normal
Backup
4
5
6
1
2
3
COM
OK
LOW
Relay (BAT LOW)
(6)-(5): ON
Battery status
output relay
LED lit
(DC ON: Green)
LED lit
(BACKUP: Red)
Relay (OPN MODE)
(1)-(2): ON
Operation mode
output relay
Indicator
COM
Normal
Backup