Troubleshooting

This page lists the errors that may occur when the S8T-DCBU-01 is used, along with their probable causes and remedies.
Check the relevant item.

When

Probable cause

Description

Remedies

Installation

S8T-DCBU-01 cannot be 
connected.

The Bus Line Connector is provided with a 
selector for preventing misconnection of 
12 V and 5 V specification S8TS units.  
For this reason, connection is not 
successful if different specification units 
are installed.

Set the selector on the Bus Line 
Connector (provided) to 24 V.
Refer to 

S8T-BUS03

 on page 4 for details.

When checking 
the 
performances
Refer to 

Checking 
Performances

 

on page 4 for 
details.

The S8T-DCBU-01 output 
indicator does not lit in 
operation check procedure, 
step 2.

The S8T-DCBU-01 operates by the output 
of the S8TS-06024

†

.  A probable cause 

is that the Bus Line Connector is not 
connected as the input voltage is 
connected by the Bus Line Connector 
(provided).

Connect the S8T-DCBU-01 to 
S8TS-06024

†

 using the Bus Line 

Connector (provided).
Refer to 

Basic Configuration

 on page 2 for 

details.

The connected S8TS-06024

†

 

does not operate in operation 
check procedure, step 2.

A probable cause is that the S8T-DCBU-
01 is connected between S8TS-06024

†

 

Basic Blocks.

The S8T-BUS03 Bus Line Connector for 
connecting the S8T-DCBU-01 is not 
connected to the AC power line.  Connect 
the S8T-DCBU-01 to the right or left end 
of S8TS-06024

†

 Basic Blocks.

The battery status indicator is 
lit even 10 seconds or more 
after the power is turned ON in 
operation check procedure, 
step 3.

A probable cause is that the battery was 
connected with the + and 

 polarities 

reversed.

Connect the battery correctly.
Refer to 

Battery Misconnection Protection 

Function

 on page 8 for details.

A probable cause is that the battery 
voltage falls below about 22.5 V. (A 
probable cause is battery discharge 
during long-term storage.)

Charge the battery before use.
Refer to 

Battery Status Indicator / Battery 

Status Output

 on page 9 for details.

A probable cause is that the backup ON/
OFF input is open.

Short the backup ON/OFF input. (Before 
shipment, the backup ON/OFF input is 
shorted.)
Refer to 

Backup ON/OFF Input Function

 

on page 8 for details.

A probable cause is that the overcurrent 
protection function of the connected 
S8TS-06024

†

 is active.

As energy is consumed by S8T-DCBU-01, 
the total load capacity of the number of 
connected S8TS-06024

†

s cannot be 

obtained.  Connect one more S8TS-
06024

†

 Basic Block.  

Refer to the 

Derating Curve

 on page 6 for 

details.

A probable cause is that the overcurrent 
protection function selector switch on the 
S8T-DCBU-01 is set low.

When three or more S8TS-06024

†

 Basic 

Blocks are connected, set the overcurrent 
protection function selector switch to 11.7 
A (typical).  (The default setting is 5.7 A 
(typical).)
Refer to 

Overcurrent Protection Function 

Selector Switch

 on page 8 for details.

A probable cause is that the output 
voltage adjustment trimmer of the 
connected S8TS-06024

†

 is set lower 

than the factory set voltage.

The S8T-DCBU-01 detects drops in the 
output voltage of the S8TS-06024

†

 and 

switches over to backup operation.  Adjust 
the output voltage adjustment trimmer on 
the S8TS-06024

†

 so that the output in a 

no-load state is 24.5 V or more.
Refer to 

Output Voltage Setting of the 

S8TS-06024

†

 on page 3 for details.

The backup operation is not 
performed in operation check 
procedure, step 5.

A probable cause is that inrush current 
during backup operation caused the fuse 
on the battery to blow.

Select a fuse taking the inrush current 
when backup operation is switched to into 
consideration.  The recommended S82Y-
TS01 Battery Holder is selected taking 
this inrush current into consideration.
Refer to 

S82Y-TS01 Battery Holder

 on 

page 3 for details.

Summary of Contents for S8T-DCBU-01

Page 1: ...n DC Backup Block See note 1 Note 1 One S8T BUS03 Connector is included as accessory 2 The output current can be selected by a switch Bus Line Connector Note One package contains 10 S8T BUS03 Connecto...

Page 2: ...on function selector switch Maximum number of S8TS 06024 Basic Blocks that can be linked Specified battery LC P122R2J LC P123R4J 5 7 A typical 2 Blocks 3 Blocks if N 1 redundant system is used Yes Yes...

Page 3: ...cause smoke or fire To prevent this place the battery on a resin battery tray 2 The inrush current shown below flows when backup operation is switched to The peak value and time of this inrush curren...

Page 4: ...Turn ON the power of battery holder 2 Turn ON the S8TS 06024 AC power line 3 Check the operating status described below after 10 seconds or more 4 Turn OFF the S8TS 06024 AC power line 5 Check that ba...

Page 5: ...s color green Battery status indicator See note 2 Yes color red Battery status output See note 2 Yes relay 24 VDC 0 1 A Backup status indicator Yes color red Operation mode output Yes relay 24 VDC 0 1...

Page 6: ...the number of connected S8TS 06024 s cannot be calculated Number of S8TS 06024 s S8TS 06024 rated input Derating curve Rated output power 1 200 to 240 VAC 1 36 W 100 to 120 VAC 2 1 1 100 to 120 VAC 2...

Page 7: ...backup time changes depending on the capacity of connected equipment ambient temperature and battery service life AC input Output voltage of the S8TS 06024 Output voltage of the S8T DCBU 01 Battery v...

Page 8: ...11 7 A typical The default setting is 5 7 A typical Overcurrent Protection Function Normal operation The overcurrent status is notified as follows LED lit Battery status indicator BAT LOW Red Relay Ba...

Page 9: ...ow When the battery is new first measure the initial backup time value Replace the battery if backup operation is not performed for the required backup time during periodic maintenance or the backup t...

Page 10: ...2 0 A Charging control circuit BAT BAT Battery Battery ON OFF input Connected to Bus Line Connector Connected to Bus Line Connector DC DC Overcurrent detection V V DC OUTPUT Operation mode output X Ba...

Page 11: ...25 114 185 7 82 Battery Holder S82Y TS01 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Track material aluminum PFP 100N PFP 50N...

Page 12: ...NC 19 DC Output Terminal V 20 Track Stopper 21 Battery Connector Terminal Block 22 Connected to Bus Line Connector 23 DC Output Terminal Block 24 Terminal Block Cover 25 Charge Voltage Selector Switch...

Page 13: ...fire Avoid use in applications where inrush current on the load side frequently occurs Doing so may result in deterioration or damage of internal elements Use Check the battery handling precautions be...

Page 14: ...irect sunlight Do not use in locations where the ambient temperature exceeds the range of the derating curve Do not use in locations where the humidity is outside the range 25 to 85 or locations subje...

Page 15: ...that the battery voltage falls below about 22 5 V A probable cause is battery discharge during long term storage Charge the battery before use Refer to Battery Status Indicator Battery Status Output o...

Page 16: ...n Provide sufficient margin for the load capacity when using the S8T DCBU 01 Wheninspecting batteries Backup time is too short A probable cause is that the battery has reached the end of its service l...

Reviews: