S8T-DCBU-01

S8T-DCBU-01

Time Charts

Startup

Note:

Backup operation is not possible during the period (7 seconds (typical)) that the
battery status output relay is LOW after the S8T-DCBU-01 is started up.

Power Failure (When the Battery Voltage does 
not Reach the BAT LOW Voltage)

Note:

Backup operation is continued for seven seconds after the power is restored from
a power failure.

Power Failure (When the Battery Voltage 
Reaches the BAT LOW Voltage)

Note:

When the battery voltage falls below 22.5 V (typical), the status of the battery
status output relay changes to LOW.

Power Failure (When the Battery Voltage 
Reaches the Overdischarge Protection Voltage)

Note:

When the battery voltage falls below 22.5 V (typical), the status of the battery
status output relay changes to LOW, when the battery voltage falls below 18.5 V
(typical), backup operation is stopped.

Backup Time (Reference Value)

Note:

1.

Backup time conditions
• Ambient temperature: 25ºC
• Battery: New product fully charged to 27.4 V 
• Length of wire between S8T-DCBU-01 and battery: 1.5 m

2.

The backup time changes depending on the capacity of connected equipment, ambient temperature, and battery service life.

AC input

Output voltage of the 
S8TS-06024

†

Output voltage of the 
S8T-DCBU-01

Battery voltage

Backup 
((1)-(2))

Operation 
mode output

Normal 
((3)-(2))

LOW 
((4)-(5))

Battery 
status output

7 seconds (typical) (See note.)

OK 
((6)-(5))

Power failure time

7 seconds (typical) 
(See note.)

AC input

Output voltage of the 
S8TS-06024

†

Output voltage of the 
S8T-DCBU-01

Battery voltage

Backup 
((1)-(2))

Operation 
mode output

Normal 
((3)-(2))

LOW 
((4)-(5))

Battery 
status output

OK 
((6)-(5))

Power failure time

7 seconds (typical) (See note.)

22.5 V (typical) (See note.)

AC input

Output voltage of the 
S8TS-06024

†

Output voltage of the 
S8T-DCBU-01

Battery voltage

Backup 
((1)-(2))

Operation 
mode output

Normal 
((3)-(2))

LOW 
((4)-(5))

Battery 
status output

OK 
((6)-(5))

22.5 V (typical) (See note.)

18.5 V (typical) (See note.)

AC input

Output voltage of the 
S8TS-06024

†

Output voltage of the 
S8T-DCBU-01

Battery voltage

Backup 
((1)-(2))

Operation 
mode output

Normal 
((3)-(2))

LOW 
((4)-(5))

Battery 
status output

OK 
((6)-(5))

80

70

60

50

40

30

20

10

0

0

25

50

75

100

Backup time (Minute)

Output capacity (W)

80

70

60

50

40

30

20

10

0

0

50

100

150

200

Backup time (Minute)

Output capacity (W)

Backup Time when LC-P122R2J is Used

Backup Time when LC-P123R4J is Used

Summary of Contents for S8T-DCBU-01

Page 1: ...n DC Backup Block See note 1 Note 1 One S8T BUS03 Connector is included as accessory 2 The output current can be selected by a switch Bus Line Connector Note One package contains 10 S8T BUS03 Connecto...

Page 2: ...on function selector switch Maximum number of S8TS 06024 Basic Blocks that can be linked Specified battery LC P122R2J LC P123R4J 5 7 A typical 2 Blocks 3 Blocks if N 1 redundant system is used Yes Yes...

Page 3: ...cause smoke or fire To prevent this place the battery on a resin battery tray 2 The inrush current shown below flows when backup operation is switched to The peak value and time of this inrush curren...

Page 4: ...Turn ON the power of battery holder 2 Turn ON the S8TS 06024 AC power line 3 Check the operating status described below after 10 seconds or more 4 Turn OFF the S8TS 06024 AC power line 5 Check that ba...

Page 5: ...s color green Battery status indicator See note 2 Yes color red Battery status output See note 2 Yes relay 24 VDC 0 1 A Backup status indicator Yes color red Operation mode output Yes relay 24 VDC 0 1...

Page 6: ...the number of connected S8TS 06024 s cannot be calculated Number of S8TS 06024 s S8TS 06024 rated input Derating curve Rated output power 1 200 to 240 VAC 1 36 W 100 to 120 VAC 2 1 1 100 to 120 VAC 2...

Page 7: ...backup time changes depending on the capacity of connected equipment ambient temperature and battery service life AC input Output voltage of the S8TS 06024 Output voltage of the S8T DCBU 01 Battery v...

Page 8: ...11 7 A typical The default setting is 5 7 A typical Overcurrent Protection Function Normal operation The overcurrent status is notified as follows LED lit Battery status indicator BAT LOW Red Relay Ba...

Page 9: ...ow When the battery is new first measure the initial backup time value Replace the battery if backup operation is not performed for the required backup time during periodic maintenance or the backup t...

Page 10: ...2 0 A Charging control circuit BAT BAT Battery Battery ON OFF input Connected to Bus Line Connector Connected to Bus Line Connector DC DC Overcurrent detection V V DC OUTPUT Operation mode output X Ba...

Page 11: ...25 114 185 7 82 Battery Holder S82Y TS01 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Track material aluminum PFP 100N PFP 50N...

Page 12: ...NC 19 DC Output Terminal V 20 Track Stopper 21 Battery Connector Terminal Block 22 Connected to Bus Line Connector 23 DC Output Terminal Block 24 Terminal Block Cover 25 Charge Voltage Selector Switch...

Page 13: ...fire Avoid use in applications where inrush current on the load side frequently occurs Doing so may result in deterioration or damage of internal elements Use Check the battery handling precautions be...

Page 14: ...irect sunlight Do not use in locations where the ambient temperature exceeds the range of the derating curve Do not use in locations where the humidity is outside the range 25 to 85 or locations subje...

Page 15: ...that the battery voltage falls below about 22 5 V A probable cause is battery discharge during long term storage Charge the battery before use Refer to Battery Status Indicator Battery Status Output o...