S8T-DCBU-01

S8T-DCBU-01

When 
S8T-DCBU-01 
is used

The backup state is not 
returned to even after the 
power is restored from a power 
failure.

A probable cause is that a protection 
function on the S8TS-06024

†

 was 

activated to stop S8TS-06024

†

 

operation.

Cancel the protection functions on the 
S8TS-06024

†

.  (Turn OFF the power of 

S8TS-06024

†

 Basic Block, and after at 

least one minute turn ON the input voltage 
again.)

Output was cut during backup 
operation.

A probable cause is that the overdischrge 
protection function was activated by 
battery voltage dropping due to discharge.

If a remedy is required during backup 
operation, allow backup to finish until the 
battery status indicator lit.

A probable cause is that an overcurrent 
state is reached due to load fluctuations 
during backup operation.

Provide sufficient margin for the load 
capacity when using the S8T-DCBU-01.

Backup operation and regular 
operation are alternately 
repeated.

A probable cause is that one of the S8TS-
06024

†

s is out of order when two or more 

S8TS-06024

†

s are connected.

Replace the out-of-order S8TS-06024

†

.

Refer to 

Backup

 on page 3 for details.

A probable cause is that the S8TS-
06024

†

 is in an overcurrent state due to 

load fluctuations during regular operation.

Provide sufficient margin for the load 
capacity when using the S8T-DCBU-01.

When inspecting 
batteries

Backup time is too short.

A probable cause is that the battery has 
reached the end of its service life.

We recommend periodically replacing the 
battery.
Refer to 

Replacing Batteries

 on page 9 for 

details.

A probable cause is that the S8T-DCBU-
01 was stored for a long time with the 
battery connected.

Storing the S8T-DCBU-01 with the battery 
connected may considerably shorten the 
service life of the battery due to leakage 
current from equipment.  When storing the 
S8T-DCBU-01, first disconnect the 
battery.

A probable cause is that battery 
characteristics caused the backup time to 
shorten in low temperatures.

Check the backup time in the operating 
environment before use.

The voltages of the two 
batteries used in series are 
considerably different.

A probable cause is a battery abnormality. Replace both batteries.

When

Probable cause

Description

Remedies

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. T000-E1-01

OMRON Corporation

Industrial Automation Company

Measuring and Supervisory Controls Department
Shiokoji Horikawa, Shimogyo-ku
Kyoto, 600-8530 Japan
Tel: (81)75-344-7108/Fax: (81)75-344-7189

Printed in Japan
0402-2M (0402) (B)

Summary of Contents for S8T-DCBU-01

Page 1: ...n DC Backup Block See note 1 Note 1 One S8T BUS03 Connector is included as accessory 2 The output current can be selected by a switch Bus Line Connector Note One package contains 10 S8T BUS03 Connecto...

Page 2: ...on function selector switch Maximum number of S8TS 06024 Basic Blocks that can be linked Specified battery LC P122R2J LC P123R4J 5 7 A typical 2 Blocks 3 Blocks if N 1 redundant system is used Yes Yes...

Page 3: ...cause smoke or fire To prevent this place the battery on a resin battery tray 2 The inrush current shown below flows when backup operation is switched to The peak value and time of this inrush curren...

Page 4: ...Turn ON the power of battery holder 2 Turn ON the S8TS 06024 AC power line 3 Check the operating status described below after 10 seconds or more 4 Turn OFF the S8TS 06024 AC power line 5 Check that ba...

Page 5: ...s color green Battery status indicator See note 2 Yes color red Battery status output See note 2 Yes relay 24 VDC 0 1 A Backup status indicator Yes color red Operation mode output Yes relay 24 VDC 0 1...

Page 6: ...the number of connected S8TS 06024 s cannot be calculated Number of S8TS 06024 s S8TS 06024 rated input Derating curve Rated output power 1 200 to 240 VAC 1 36 W 100 to 120 VAC 2 1 1 100 to 120 VAC 2...

Page 7: ...backup time changes depending on the capacity of connected equipment ambient temperature and battery service life AC input Output voltage of the S8TS 06024 Output voltage of the S8T DCBU 01 Battery v...

Page 8: ...11 7 A typical The default setting is 5 7 A typical Overcurrent Protection Function Normal operation The overcurrent status is notified as follows LED lit Battery status indicator BAT LOW Red Relay Ba...

Page 9: ...ow When the battery is new first measure the initial backup time value Replace the battery if backup operation is not performed for the required backup time during periodic maintenance or the backup t...

Page 10: ...2 0 A Charging control circuit BAT BAT Battery Battery ON OFF input Connected to Bus Line Connector Connected to Bus Line Connector DC DC Overcurrent detection V V DC OUTPUT Operation mode output X Ba...

Page 11: ...25 114 185 7 82 Battery Holder S82Y TS01 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Track material aluminum PFP 100N PFP 50N...

Page 12: ...NC 19 DC Output Terminal V 20 Track Stopper 21 Battery Connector Terminal Block 22 Connected to Bus Line Connector 23 DC Output Terminal Block 24 Terminal Block Cover 25 Charge Voltage Selector Switch...

Page 13: ...fire Avoid use in applications where inrush current on the load side frequently occurs Doing so may result in deterioration or damage of internal elements Use Check the battery handling precautions be...

Page 14: ...irect sunlight Do not use in locations where the ambient temperature exceeds the range of the derating curve Do not use in locations where the humidity is outside the range 25 to 85 or locations subje...

Page 15: ...that the battery voltage falls below about 22 5 V A probable cause is battery discharge during long term storage Charge the battery before use Refer to Battery Status Indicator Battery Status Output o...

Page 16: ...n Provide sufficient margin for the load capacity when using the S8T DCBU 01 Wheninspecting batteries Backup time is too short A probable cause is that the battery has reached the end of its service l...

Reviews: