6
S8T-DCBU-01
S8T-DCBU-01
Engineering Data
■
Derating Curve
Note:
1.
Add one more S8TS-06024
Basic Block if a redundant system is used.
2.
If there is a derating problem, use forced air-cooling.
3.
The ambient temperature is specified for a point 50 mm below the power supply.
4.
The ambient temperature range of the battery is 0 to 40ºC, different from that for the S8T-DCBU-01.
The ambient temperature of the battery is specified according to the battery's surface temperature.
5.
As energy is consumed by S8T-DCBU-01, the total output capacity of the number of connected S8TS-06024
s cannot be
calculated.
Number of S8TS-06024
s
S8TS-06024
rated input
Derating curve
Rated output power
1
200 to 240 VAC
*1
36 W
100 to 120 VAC
*2
1 (+1)
100 to 120 VAC/200 to 240 VAC *3
30 W
2
*4
88.8 W
2 (+1)
*5
76.8 W
3
*6
146.4 W
3 (+1)
*7
128.4 W
4
*8
192 W
4 (+1)
*9
168 W
40
35
30
25
20
15
10
5
0
−
20
−
10
0
10
20
30
40
50
60
*2
*3
*1
36
Output power (W)
Ambient temperature (˚C)
100
80
60
40
20
0
−
20
−
10
0
10
20
30
40
50
60
*4
*5
88.8
76.8
Output power (W)
Ambient temperature (˚C)
160
140
120
100
80
60
40
20
0
−
20
−
10
0
10
20
30
40
50
60
*6
*7
146.4
128.4
Output power (W)
Ambient temperature (˚C)
S8T-DCBU-01
S8T-DCBU-01
S8T-DCBU-01
200
150
100
50
0
−
20
−
10
0
10
20
30
40
50
60
*8
*9
192
168
Output power (W)
Ambient temperature (˚C)
S8T-DCBU-01