S8BA-LF

15

(for maintenance)

When maintaining the connected equipment, turn OFF 
the unit’s “Power” switch to stop the output, and stop the 
supply of the “input power supply”.

Even if the input power supply to the UPS is stopped 
while it is in operation, the power output of his unit 
does not stop and power is supplied from the battery.

Do not disassemble, repair, or modify the unit.

Doing so may cause an electric shock or a fire.

If fluid leaks from the interior, do not touch the fluid.

Doing so may cause blindness or burns.

If the fluid contacts your eyes or skin, wash it out with 
lots of clean water and consult your doctor.

Do not throw the unit into fire.

Since the battery is incorporated in the unit, the 
insulator may melt, the gas exhaust valve or protection 
mechanism may be damaged, or the electrolyte may 
catch fire, and it may result eventually in an abnormal 
heating, smoke, rupture or fire.

Do not insert metal objects into the input terminal block 
and the output terminal block of the UPS.

Doing so may result in electric shock.

Do not insert metal objects into the battery connectors.
Do not short between the connector terminals.

Doing so may result in electric shock.

The battery's protection board may be damaged due 
to a short-circuit.

(for battery replacement)

Risk of explosion if battery is  replaced by an incorrect 
type.

Not doing so may cause a fire.

Battery pack for; product model: S8BA-B120L.

Do not replace the battery in a place where there is 
flammable gas.

Spark may occur when connecting the battery, which 
may cause an explosion or fire.

If fluid leaks from the battery, do not touch the fluid.

Doing so may cause blindness or burns.

If the fluid contacts your eyes or skin, wash it out with 
lots of clean water and consult your doctor.

Do not disassemble or modify the battery.

A safety mechanism and protection mechanism to 
prevent danger are embedded into the battery. If they 
are damaged, it may cause an abnormal heating, 
smoke, rupture or fire on the battery.

Do not drop the battery and do not expose it to strong 
impact.

Doing so may cause a leakage, abnormal heating, 
smoke, rupture or fire on the battery. And, if the 
battery's protection mechanism is broken, the battery 
may be charged at an abnormal current or voltage, an 
abnormal chemical reaction may occur inside the 
battery, and it may result eventually in an abnormal 
heating, smoke, rupture or fire.

Do not short the battery with metal objects.

Doing so could cause an electric shock, fire or burn.

Some electrical energy still remains inside the spent 
battery.

Do not dispose of battery in a fire or damage battery.

The insulator inside the battery may melt, the gas 
exhaust valve or protection mechanism may be 
damaged, or the electrolyte may catch fire, and it may 
result eventually in abnormal heating, smoke, rupture 
or fire.

Do not use a new battery and an old battery at the same 
time.

The battery may be excessively discharged while 
being used or excessively charged while being 
charged, an abnormal chemical reaction may occur 
inside the battery, and it may result eventually in an 
abnormal heating, smoke, rupture or fire.

A battery can present a risk of electrical shock and 
high short circuit current.

Contact with any part of a grounded battery can result 
in electrical shock.

The following precautions should be observed when 
working on batteries:
(a) Remove watches, rings, or other metal objects.
(b) Use screwdrivers with insulated handles.
(c) Wear rubber gloves and boots.
(d) Do not lay tools or metal parts on top of batteries.
(e) Remove the connection from ground if any part of 

the battery is determined to be grounded.

Dispose of or collect (recycle) the battery according to 
your own rules set for that purpose or as instructed by 
laws and regulations. 
Do not dispose of it in fire. Otherwise, it could explode. 

Before using

Charge the battery soon after purchasing the unit.

If not used for a long time after being purchased, the UPS may 
become unusable because the characteristics of its battery 
become inferior.

Connect the UPS to the input power supply and turn ON the 
“Power” switch to charge the battery.

If the UPS is moved from a warm place to a cold place, start using it 
after leaving it as-is for a few hours.

If the UPS is suddenly moved to a warm place, water may adhere 
to it (condensation). In such a case, if power is supplied without 
checking the condition, the UPS may be damaged.

Take measures against the unexpected events such as protecting 
data and making the system redundant.

The UPS may stop its power due to failure.

For Connection

Be careful not to let a short-circuit occur between output lines of the 
UPS and not to let an output line and the ground be short-circuited (a 
ground fault).

Otherwise, the UPS may be damaged.

To transfer or sell the UPS to a third party, attach all the documents 
and other accessories contained in the product package to the UPS. 
It is supposed that the UPS is to be used in accordance with the 
conditions specified in the attached documents.

While Using the UPS

Turn OFF the “Power” switch of the UPS before turning OFF the input 
power supply.

When the input power supply is stopped, backup operation starts.

If the frequency of backup operation becomes high, the battery life 
may be significantly reduced.

Do not use the UPS for purposes requiring frequent backup operation.

The battery will deteriorate and become unable to last for the 
specified backup time.

Precautions for Safe Use

廢電池請回收

Summary of Contents for S8BA LF Series

Page 1: ...Model Number Legend Use the following format to place an order Ordering Information Main body Uninterruptible Power Supply UPS 16 7 A 400 W for use as a UL compliant device Communication cable Replac...

Page 2: ...play cancellation at a load equal to or below the rated capacity normal operation backup operation Battery Type Lithium ion battery Rated voltage 14 4 VDC Rated capacity 1600 mAh 1 parallel 1600 mAh 2...

Page 3: ...ad lines V V 3 DC input terminal block Connect to input lines V V 4 GR terminal Ground this terminal to less than 100 to improve noise resistance and prevent electrical shock 5 USB port Connect to a U...

Page 4: ...0 W S8BA 24D24D240LF 240 W S8BA 24D24D360LF 360 W S8BA 24D24D480LF 480 W No Name Function 11 DIN rail mounting hook Hook the UPS on the DIN rail 12 DIN rail mounting groove Groove for positioning the...

Page 5: ...wire Twisted pair 0 5 mm2 AWG AWG20 10 A Solid wire Twisted pair 0 75 mm2 AWG AWG16 15 A Solid wire Twisted pair 1 25 mm2 AWG AWG14 20 A Solid wire Twisted pair 2 0 mm2 AWG AWG12 Temperature rating f...

Page 6: ...the UPS is stopped after the time period specified in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected cont...

Page 7: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 8: ...the total capacity of the connected devices 3 Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial...

Page 9: ...20 0 Ambient temperature C Load rate A For standard mounting B For face up mounting stationary mounting A C B 0 10 20 30 40 50 60 120 100 80 60 40 20 0 Ambient temperature C Load rate A For standard m...

Page 10: ...s During power failure Power switch Battery level UPS output Indication in the status display Beeper UPS operating mode BU signal OUT BL signal OUT BS signal IN Normal operation Backup operation ON ON...

Page 11: ...2 In normal operation the output stops when the input protection fuse blows out Dimensions Unit mm Main body 0 20 40 60 80 100 0 20 40 60 80 100 120 In backup operation Output current Output voltage 1...

Page 12: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 13: ...imary power supply before connecting the unit to the input power supply terminal When connecting a cable to the terminal block use a cable that complies with the input current specification of the UPS...

Page 14: ...ct with water If you drop the unit stop using it Doing so may cause an electric shock or a fire Doing so may cause an abnormal heating smoke rupture or fire on the battery If the unit becomes wet or i...

Page 15: ...nside the battery may melt the gas exhaust valve or protection mechanism may be damaged or the electrolyte may catch fire and it may result eventually in abnormal heating smoke rupture or fire Do not...

Page 16: ...main body and use the UPS in an operating condition below the derating curve During machining work for mounting make sure that no metal scrap goes into the product The heat dissipation of the UPS may...

Page 17: ...ll machine conform to EMC standards Applicable EMC Electromagnetic Compatibility standards are as follows EMS Electromagnetic Susceptibility EN 61000 6 2 EMI Electromagnetic Interference EN 61000 6 4...

Page 18: ...xpressly approved by the party responsible for compliance could void the user s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class A digi...

Page 19: ...he USB RS 232C I O port installed in the UPS Two types of batteries are selectable for the 480W allowing the ideal backup time to be realized A wide lineup culminating in the 960W makes it possible to...

Page 20: ...Communication cable Input voltage Output voltage Output current capacity Model number 24 VDC 24 VDC 20 A 480 W S8BA 24D24D480SBF 40 A 960 W S8BA 24D24D960SBF Rated voltage Rated capacity Weight Model...

Page 21: ...cteristics 6 min constant power rated load The backup time can be set from the mode selection backup operation time selection switch or the shutdown software Environme nt Operating environment tempera...

Page 22: ...han specified time 4 Conditions With rated loads connected at a rated input voltage and at a full battery charge 5 Conditions With rated loads connected at a rated input voltage and at maximum battery...

Page 23: ...ck 6 Battery communication port 3 Battery connection terminal block 7 Mode selection Backup time setting switch 4 LED indicators 8 RS232C USB port DC ON LED BATT LED ALERT LED Positive terminal Negati...

Page 24: ...S8BA SBF 24 Rear view S8BA 24D24D480SBF S8BA S480L S8BA 24D24D960SBF S8BA S960L 9 9 No Name 9 DIN rail hook 9 9 No Name 9 DIN rail hook...

Page 25: ...and recommended cable sizes see the following table 20 A 40 A Connectable sizes Cable Solid wire 0 2 to 10 mm2 0 75 to 16 0 mm2 Stranded wire 0 2 to 6 mm2 AWG AWG 8 to 24 AWG 6 to 18 Stripped cable le...

Page 26: ...ied in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected contact or the ON OFF status of the open collector c...

Page 27: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 28: ...e backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial values for products that have not been used at 25 C The backup time becomes sho...

Page 29: ...Contact mounting Less than 15 mm space between the left and right 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load rate 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load...

Page 30: ...ge 26 Overcurrent protection curve 480 W 960 W Durling power failure Input power supply Output from UPS UPS operating mode Normal operation Backup operation BU signal OUT BL signal OUT BS signal IN Ba...

Page 31: ...1 Dimensions Unit mm Control unit Battery unit S8BA 24D24D480SBF 124 9 5 31 99 4 44 111 4 S8BA 24D24D960SBF 9 5 52 124 111 4 31 99 4 111 4 9 5 30 7 80 124 99 4 S8BA S480L 111 4 9 5 150 124 30 7 99 4 S...

Page 32: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 33: ...ch to BATT REP and when the LED changes from a fast blink to a slow blink shut off the input power When performing maintenance on the connected devices follow the above instructions to ensure safety W...

Page 34: ...or more above the top and below the bottom Do not connect the RS232C USB port or the CONTACT port to a LAN device using a LAN cable Connection to a LAN device may result in malfunction in or damage t...

Page 35: ...he input terminal block and the output terminal block of the UPS Doing so may result in electric shock Do not insert metal objects into the battery connectors Do not short between the connector termin...

Page 36: ...is left unused in the above state for 3 months or longer the battery goes into overdischarge state and the backup time may become shorter or the battery may become unusable Storing Storing the battery...

Page 37: ...schedule and frequency Applicable directives EMC Directives Low Voltage Directives Principles regarding conformance OMRON electronic devices that comply with EC Directives also conform to the related...

Page 38: ...f radio interference occurs the user may be required to take appropriate measures Conformance to UL This product must be installed within a control panel with an internal heater or other unit to prote...

Page 39: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 40: ...2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA...

Reviews: