S8BA-LF

2

Ratings, Characteristics, and Functions

*1.

An estimated value for standard mounting. Not a guaranteed value.

*2.

Conditions: With rated loads connected, at a rated input voltage, and with the battery fully charged.

*3.

Conditions: With rated loads connected, at a rated input voltage, and at the maximum battery charging current.

*4.

400 W for use as a UL compliant device.

*5.

20 A for use as a UL compliant device.

*6.

16.7 A for use as a UL compliant device.

*7.

When using in an environment at a high temperature, charging may be paused by charging temperature protection, then the charging time will 
be longer than specified time.
"CS" will be displayed when charging temperature protection is operated.

*8.

For the S8BA-24D24D120LF, install all of the RSMN-2030, RSHN-2030, and RSEN-2030 EMC filters manufactured by TDK. For the S8BA-
24D24D240LF, S8BA-24D24D360LF, or S8BA-24D24D480LF, install both the RSMN-2030 and RSHN-2030 or their equivalents. Install these 
filters in series to the cable connected to the DC input terminal block.
When you do, do not connect anything to the GR terminal.
The effectiveness of the noise filters may be affected by the installation environment. Be sure to check effectiveness before starting operation.

Item

Capacity

120 W

240 W

360 W

480 W *4

DC input

Rated input voltage

24 VDC

Input 
voltage 
range

When standard voltage 
sensitivity is set

24 VDC±10%

When low voltage sensitivity 
is set

24 VDC±12.5%

When high voltage 
sensitivity is set

24 VDC±5%

Input 
maximum 
current

for rated input voltage for 
rated loads connected

5.9 A

11.7 A

17.5 A

23.3 A *5

Input terminal

Push-in terminal block

Input protection

Fuse (cannot be replaced by the customer)

Input protection capacity

10 A

15 A

30 A

DC output

Rated 
current

(for rated output voltage)

5 A

10 A

15 A

20 A *6

Switching time

Uninterrupted

Output 
voltage

Normal operation

Output of input voltage as-is

Backup operation

24 V±5%

Output terminal

Push-in terminal block

Overload protection

Alarm display at a load level of 110% or over (normal operation)

Alarm display at a load level of 110% or over and output voltage drop (backup operation)

Alarm display cancellation at a load equal to or below the rated capacity (normal operation, backup 
operation)

Battery

Type

Lithium-ion battery

Rated voltage

14.4 VDC

Rated capacity

1600 mAh × 1 parallel

1600 mAh × 2 parallel

1600 mAh × 3 parallel

1600 mAh × 4 parallel

Expected battery life *1

2.5 years (50°C), 5 years (40°C), 10 years (25°C)

Replacement by user

Yes (Hot swapping)

Auto battery check function

Yes

Battery life counter function

Yes

Charging time

4 hours *7

Backup time (25°C, initial characteristics)

6 min. (120 W)

6 min. (240 W)

6 min. (360 W)

6 min. (480 W)

Environment

Operating ambient temperature/humidity

0 to +55°C/10 to 90% (with no condensation)

Storage ambient temperature/humidity

–20°to +55°C/10 to 90% (with no condensation)

Vibration resistance

JIS C 60068-2-6 compliant.  5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz acceleration rate: 9.8 m/s

2

X, Y, and Z directions for 100 minutes (Time coefficient: 10 minutes × coefficient factor 10 = total time 100 min.)

Shock resistance

JIS C 60068-2-27 compliant. 147 m/s

2

, 3 times in X, Y, and Z directions.

Structure

Dimensions (W × D × H mm)

94 × 100 × 100

148 × 100 × 100

270 × 100 × 100

Weight of unit

Approx. 0.8 kg

Approx. 1.3 kg

Approx. 2.0 kg

Approx. 2.3 kg

Cooling method

Natural cooling

Insulation and 
withstand 
voltage

Withstand voltage

1,000 V 50/60 Hz AC between the DC external terminals and the GR terminal for 1 minute at a leakage 
current of 10 mA max.

Insulation resistance

20 M

Ω

 min. between the DC external terminals and the GR terminal (at 500 VDC)

Compliance 
to standard

Safety standard

UL508/CE/C22.2 No.107.1-01 / EAC

EMI

Radiated disturbance 
electromagnetic field strength

EN61000-6-4/FCC/ICES/RCM/KC

Ship standard

LR/ABS/EN60945 *8/DNV GL

Internal power consumption (normal *2 / maximum *3)

7 W/22 W

11 W/41 W

14 W/60 W

18 W/80 W

Serial 
communication

RS-232C (Interface terminal)

Yes (RJ45)

USB (interface terminal)

Yes (B connector)

I/O signal (Interface terminal)

Yes (RJ45)

Accessories

USB cable (1.5 m)

Accessory functions

Beeper setting; Auto restart setting; Auto test setting; Auto restart mode setting; Input sensitivity setting; 
Remote ON/OFF signal logic setting; Cold start setting; Battery life counter setting; Power switch function 
setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time 
setting; Backup (BU) signal delay time setting; and Contact signal I/O test

Summary of Contents for S8BA LF Series

Page 1: ...Model Number Legend Use the following format to place an order Ordering Information Main body Uninterruptible Power Supply UPS 16 7 A 400 W for use as a UL compliant device Communication cable Replac...

Page 2: ...play cancellation at a load equal to or below the rated capacity normal operation backup operation Battery Type Lithium ion battery Rated voltage 14 4 VDC Rated capacity 1600 mAh 1 parallel 1600 mAh 2...

Page 3: ...ad lines V V 3 DC input terminal block Connect to input lines V V 4 GR terminal Ground this terminal to less than 100 to improve noise resistance and prevent electrical shock 5 USB port Connect to a U...

Page 4: ...0 W S8BA 24D24D240LF 240 W S8BA 24D24D360LF 360 W S8BA 24D24D480LF 480 W No Name Function 11 DIN rail mounting hook Hook the UPS on the DIN rail 12 DIN rail mounting groove Groove for positioning the...

Page 5: ...wire Twisted pair 0 5 mm2 AWG AWG20 10 A Solid wire Twisted pair 0 75 mm2 AWG AWG16 15 A Solid wire Twisted pair 1 25 mm2 AWG AWG14 20 A Solid wire Twisted pair 2 0 mm2 AWG AWG12 Temperature rating f...

Page 6: ...the UPS is stopped after the time period specified in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected cont...

Page 7: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 8: ...the total capacity of the connected devices 3 Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial...

Page 9: ...20 0 Ambient temperature C Load rate A For standard mounting B For face up mounting stationary mounting A C B 0 10 20 30 40 50 60 120 100 80 60 40 20 0 Ambient temperature C Load rate A For standard m...

Page 10: ...s During power failure Power switch Battery level UPS output Indication in the status display Beeper UPS operating mode BU signal OUT BL signal OUT BS signal IN Normal operation Backup operation ON ON...

Page 11: ...2 In normal operation the output stops when the input protection fuse blows out Dimensions Unit mm Main body 0 20 40 60 80 100 0 20 40 60 80 100 120 In backup operation Output current Output voltage 1...

Page 12: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 13: ...imary power supply before connecting the unit to the input power supply terminal When connecting a cable to the terminal block use a cable that complies with the input current specification of the UPS...

Page 14: ...ct with water If you drop the unit stop using it Doing so may cause an electric shock or a fire Doing so may cause an abnormal heating smoke rupture or fire on the battery If the unit becomes wet or i...

Page 15: ...nside the battery may melt the gas exhaust valve or protection mechanism may be damaged or the electrolyte may catch fire and it may result eventually in abnormal heating smoke rupture or fire Do not...

Page 16: ...main body and use the UPS in an operating condition below the derating curve During machining work for mounting make sure that no metal scrap goes into the product The heat dissipation of the UPS may...

Page 17: ...ll machine conform to EMC standards Applicable EMC Electromagnetic Compatibility standards are as follows EMS Electromagnetic Susceptibility EN 61000 6 2 EMI Electromagnetic Interference EN 61000 6 4...

Page 18: ...xpressly approved by the party responsible for compliance could void the user s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class A digi...

Page 19: ...he USB RS 232C I O port installed in the UPS Two types of batteries are selectable for the 480W allowing the ideal backup time to be realized A wide lineup culminating in the 960W makes it possible to...

Page 20: ...Communication cable Input voltage Output voltage Output current capacity Model number 24 VDC 24 VDC 20 A 480 W S8BA 24D24D480SBF 40 A 960 W S8BA 24D24D960SBF Rated voltage Rated capacity Weight Model...

Page 21: ...cteristics 6 min constant power rated load The backup time can be set from the mode selection backup operation time selection switch or the shutdown software Environme nt Operating environment tempera...

Page 22: ...han specified time 4 Conditions With rated loads connected at a rated input voltage and at a full battery charge 5 Conditions With rated loads connected at a rated input voltage and at maximum battery...

Page 23: ...ck 6 Battery communication port 3 Battery connection terminal block 7 Mode selection Backup time setting switch 4 LED indicators 8 RS232C USB port DC ON LED BATT LED ALERT LED Positive terminal Negati...

Page 24: ...S8BA SBF 24 Rear view S8BA 24D24D480SBF S8BA S480L S8BA 24D24D960SBF S8BA S960L 9 9 No Name 9 DIN rail hook 9 9 No Name 9 DIN rail hook...

Page 25: ...and recommended cable sizes see the following table 20 A 40 A Connectable sizes Cable Solid wire 0 2 to 10 mm2 0 75 to 16 0 mm2 Stranded wire 0 2 to 6 mm2 AWG AWG 8 to 24 AWG 6 to 18 Stripped cable le...

Page 26: ...ied in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected contact or the ON OFF status of the open collector c...

Page 27: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 28: ...e backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial values for products that have not been used at 25 C The backup time becomes sho...

Page 29: ...Contact mounting Less than 15 mm space between the left and right 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load rate 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load...

Page 30: ...ge 26 Overcurrent protection curve 480 W 960 W Durling power failure Input power supply Output from UPS UPS operating mode Normal operation Backup operation BU signal OUT BL signal OUT BS signal IN Ba...

Page 31: ...1 Dimensions Unit mm Control unit Battery unit S8BA 24D24D480SBF 124 9 5 31 99 4 44 111 4 S8BA 24D24D960SBF 9 5 52 124 111 4 31 99 4 111 4 9 5 30 7 80 124 99 4 S8BA S480L 111 4 9 5 150 124 30 7 99 4 S...

Page 32: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 33: ...ch to BATT REP and when the LED changes from a fast blink to a slow blink shut off the input power When performing maintenance on the connected devices follow the above instructions to ensure safety W...

Page 34: ...or more above the top and below the bottom Do not connect the RS232C USB port or the CONTACT port to a LAN device using a LAN cable Connection to a LAN device may result in malfunction in or damage t...

Page 35: ...he input terminal block and the output terminal block of the UPS Doing so may result in electric shock Do not insert metal objects into the battery connectors Do not short between the connector termin...

Page 36: ...is left unused in the above state for 3 months or longer the battery goes into overdischarge state and the backup time may become shorter or the battery may become unusable Storing Storing the battery...

Page 37: ...schedule and frequency Applicable directives EMC Directives Low Voltage Directives Principles regarding conformance OMRON electronic devices that comply with EC Directives also conform to the related...

Page 38: ...f radio interference occurs the user may be required to take appropriate measures Conformance to UL This product must be installed within a control panel with an internal heater or other unit to prote...

Page 39: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 40: ...2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA...

Reviews: