S8BA-SBF

34

Do not use the unit at a location where the operating 
environment temperature is more than 55°C

The battery deteriorates rapidly. It may result in fire.

If the battery's resin separator is damaged, the battery 
may be short-circuited inside, and may cause an 
abnormal heating, smoke, rupture or fire.

Doing so may cause a failure or malfunction of the unit.

Do not exceed the ranges specified for environmental 
conditions during use/storage.
Do not install or store the unit in the places listed below.

Do not store in places where the humidity is lower than 
10% or higher than 90%.

Do not use the unit in places where the ambient 
temperature is lower than 0

°C

 or higher than 55

°C

(With no condensation)

Do not use in places where the humidity is lower than 
10% or higher than 90%.

Do not install/store the unit in closed places such as 
cabinets with no clearance, places where there is 
flammable or corrosive gas, places with large amounts 
of dust, places exposed to direct sunlight, places 
exposed to shock or vibration, salty or wet places, or 
outdoors.

Installation or storing the unit in such a place may 
cause a fire.

When you use plug strip and other plugs to connect 
additional devices, do not connect devices that exceed 
the current capacity of the available plugs.

The current protection of the unit may operate, which 
may stop the output.

The cable heats up, which may cause a fire.

Do not use a cable with damaged insulation.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.

Doing so may cause the cable to be damaged or 
heated, which may cause an electric shock or a fire.

If the cable is damaged, stop using the unit and have the cable 
repaired.

For repair, contact our sales personnel.

Do not connect any devices other than rated voltage is 24 
VDC.

The rated output voltage of this unit is 24 VDC.

Overvoltage or overcurrent may damage the 
connected devices.

The output voltage range is 22 to 30 VDC.

All of the included accessories are designed to be used 
with the unit. Do not use the accessories with other 
devices.

Doing so may compromise the safety of devices.

When this product is used in compliance with CE 
marking, please use under 2 m communication cable.

Do not block the air vents (upper and lower).

Doing so will cause the internal temperature to rise, 
which may cause the unit to fail and the battery to 
deteriorate.

During installation, leave a space of 50 mm or more 
above the top and below the bottom.

Do not connect the RS232C/USB port or the CONTACT 
port to a LAN device using a LAN cable.

Connection to a LAN device may result in malfunction 
in or damage to the UPS or the LAN device.

Do not run this unit in parallel.

Operating this unit in parallel may cause a failure or 
malfunction.

(for use)

Do not allow the unit to come in contact with water. 

Doing so may cause an electric shock or a fire.

Doing so may cause an abnormal heating, smoke, 
rupture, or fire on the battery.

If the unit comes in contact with water, immediately 
stop using it and have it inspected and repaired. To 
make an emergency stop, turn the rotary switch to 
"BATT REP" and turn off the input power after the LED 
changes from fast blinking to slow blinking.

For repair, contact our sales personnel.

When the battery unit is dead, replace it immediately or 
stop using the unit.

Continuing the use of it may cause fire or electric 
shock due to liquid leaks.

*

The values in the table are the expected life under 
standard use conditions and are not guaranteed.

Occasionally, wipe off dust on the input terminal block 
and the output terminal block with a dry cloth.

Accumulated dust may cause a fire. 
Before wiping off dust, stop all connected devices and 
the unit, and stop the supply of commercial power.
The unit will stop after 30 seconds of setting the mode selection/
backup operation time selection switch to "0.5".

Do not use the unit in a closed place and do not cover the 
unit.

Doing so may cause abnormal heating or a fire.

If you notice something unusual such as abnormal sound 
or smell, discoloration, deformation, and heating, turn 
OFF the unit's power and stop the supply from the input 
power supply.
To make an emergency stop, move the rotary switch to 
"BATT REP", and when the LED changes from a fast 
blink to a slow blink, shut off the input power.

Using the unit under such conditions may cause an 
abnormal heating, rupture or fire.

If you notice such a condition, stop using the unit and 
contact our sales personnel for inspection and repairs.

If fluid leaks from the interior, do not touch the fluid.

Doing so may cause blindness or burns.

If the fluid contacts your eyes or skin, wash it out with 
lots of clean water and consult your doctor. The fluid 
may damage your eye if your eye is left untreated.

Do not place any objects on the unit, and do not drop 
heavy objects onto the unit.

Doing so may cause distortion/damage to the case or 
a failure of the internal circuit, which may cause a fire.

Ambient temperature

Expected life

25°C

10 years

35°C

6.7 years

45°C

3.7 years

55°C

1.9 years

Summary of Contents for S8BA LF Series

Page 1: ...Model Number Legend Use the following format to place an order Ordering Information Main body Uninterruptible Power Supply UPS 16 7 A 400 W for use as a UL compliant device Communication cable Replac...

Page 2: ...play cancellation at a load equal to or below the rated capacity normal operation backup operation Battery Type Lithium ion battery Rated voltage 14 4 VDC Rated capacity 1600 mAh 1 parallel 1600 mAh 2...

Page 3: ...ad lines V V 3 DC input terminal block Connect to input lines V V 4 GR terminal Ground this terminal to less than 100 to improve noise resistance and prevent electrical shock 5 USB port Connect to a U...

Page 4: ...0 W S8BA 24D24D240LF 240 W S8BA 24D24D360LF 360 W S8BA 24D24D480LF 480 W No Name Function 11 DIN rail mounting hook Hook the UPS on the DIN rail 12 DIN rail mounting groove Groove for positioning the...

Page 5: ...wire Twisted pair 0 5 mm2 AWG AWG20 10 A Solid wire Twisted pair 0 75 mm2 AWG AWG16 15 A Solid wire Twisted pair 1 25 mm2 AWG AWG14 20 A Solid wire Twisted pair 2 0 mm2 AWG AWG12 Temperature rating f...

Page 6: ...the UPS is stopped after the time period specified in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected cont...

Page 7: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 8: ...the total capacity of the connected devices 3 Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial...

Page 9: ...20 0 Ambient temperature C Load rate A For standard mounting B For face up mounting stationary mounting A C B 0 10 20 30 40 50 60 120 100 80 60 40 20 0 Ambient temperature C Load rate A For standard m...

Page 10: ...s During power failure Power switch Battery level UPS output Indication in the status display Beeper UPS operating mode BU signal OUT BL signal OUT BS signal IN Normal operation Backup operation ON ON...

Page 11: ...2 In normal operation the output stops when the input protection fuse blows out Dimensions Unit mm Main body 0 20 40 60 80 100 0 20 40 60 80 100 120 In backup operation Output current Output voltage 1...

Page 12: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 13: ...imary power supply before connecting the unit to the input power supply terminal When connecting a cable to the terminal block use a cable that complies with the input current specification of the UPS...

Page 14: ...ct with water If you drop the unit stop using it Doing so may cause an electric shock or a fire Doing so may cause an abnormal heating smoke rupture or fire on the battery If the unit becomes wet or i...

Page 15: ...nside the battery may melt the gas exhaust valve or protection mechanism may be damaged or the electrolyte may catch fire and it may result eventually in abnormal heating smoke rupture or fire Do not...

Page 16: ...main body and use the UPS in an operating condition below the derating curve During machining work for mounting make sure that no metal scrap goes into the product The heat dissipation of the UPS may...

Page 17: ...ll machine conform to EMC standards Applicable EMC Electromagnetic Compatibility standards are as follows EMS Electromagnetic Susceptibility EN 61000 6 2 EMI Electromagnetic Interference EN 61000 6 4...

Page 18: ...xpressly approved by the party responsible for compliance could void the user s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class A digi...

Page 19: ...he USB RS 232C I O port installed in the UPS Two types of batteries are selectable for the 480W allowing the ideal backup time to be realized A wide lineup culminating in the 960W makes it possible to...

Page 20: ...Communication cable Input voltage Output voltage Output current capacity Model number 24 VDC 24 VDC 20 A 480 W S8BA 24D24D480SBF 40 A 960 W S8BA 24D24D960SBF Rated voltage Rated capacity Weight Model...

Page 21: ...cteristics 6 min constant power rated load The backup time can be set from the mode selection backup operation time selection switch or the shutdown software Environme nt Operating environment tempera...

Page 22: ...han specified time 4 Conditions With rated loads connected at a rated input voltage and at a full battery charge 5 Conditions With rated loads connected at a rated input voltage and at maximum battery...

Page 23: ...ck 6 Battery communication port 3 Battery connection terminal block 7 Mode selection Backup time setting switch 4 LED indicators 8 RS232C USB port DC ON LED BATT LED ALERT LED Positive terminal Negati...

Page 24: ...S8BA SBF 24 Rear view S8BA 24D24D480SBF S8BA S480L S8BA 24D24D960SBF S8BA S960L 9 9 No Name 9 DIN rail hook 9 9 No Name 9 DIN rail hook...

Page 25: ...and recommended cable sizes see the following table 20 A 40 A Connectable sizes Cable Solid wire 0 2 to 10 mm2 0 75 to 16 0 mm2 Stranded wire 0 2 to 6 mm2 AWG AWG 8 to 24 AWG 6 to 18 Stripped cable le...

Page 26: ...ied in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected contact or the ON OFF status of the open collector c...

Page 27: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 28: ...e backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial values for products that have not been used at 25 C The backup time becomes sho...

Page 29: ...Contact mounting Less than 15 mm space between the left and right 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load rate 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load...

Page 30: ...ge 26 Overcurrent protection curve 480 W 960 W Durling power failure Input power supply Output from UPS UPS operating mode Normal operation Backup operation BU signal OUT BL signal OUT BS signal IN Ba...

Page 31: ...1 Dimensions Unit mm Control unit Battery unit S8BA 24D24D480SBF 124 9 5 31 99 4 44 111 4 S8BA 24D24D960SBF 9 5 52 124 111 4 31 99 4 111 4 9 5 30 7 80 124 99 4 S8BA S480L 111 4 9 5 150 124 30 7 99 4 S...

Page 32: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 33: ...ch to BATT REP and when the LED changes from a fast blink to a slow blink shut off the input power When performing maintenance on the connected devices follow the above instructions to ensure safety W...

Page 34: ...or more above the top and below the bottom Do not connect the RS232C USB port or the CONTACT port to a LAN device using a LAN cable Connection to a LAN device may result in malfunction in or damage t...

Page 35: ...he input terminal block and the output terminal block of the UPS Doing so may result in electric shock Do not insert metal objects into the battery connectors Do not short between the connector termin...

Page 36: ...is left unused in the above state for 3 months or longer the battery goes into overdischarge state and the backup time may become shorter or the battery may become unusable Storing Storing the battery...

Page 37: ...schedule and frequency Applicable directives EMC Directives Low Voltage Directives Principles regarding conformance OMRON electronic devices that comply with EC Directives also conform to the related...

Page 38: ...f radio interference occurs the user may be required to take appropriate measures Conformance to UL This product must be installed within a control panel with an internal heater or other unit to prote...

Page 39: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 40: ...2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA...

Reviews: