53
Reference
References
A. Specifications
90 to 110 VAC
(during backup
operation)
90 to 110 VAC
(during backup
operation)
100V mode
90 to 110 VAC
110V mode
100 to 120 VAC
115V mode
105 to 120 VAC
120V mode
105 to 120 VAC
(During backup operation)
100V mode
90 to 110 VAC
110V mode
100 to 120 VAC
115V mode
105 to 120 VAC
120V mode
105 to 120 VAC
(During backup operation)
86 + 4 to 114 +
4
VAC
BX35F
BX50F
BX50FW
BX75SW
Method
Operation method
Connectable devices
Input voltage
range
Frequency
Maximum current
8A
12A
12A
12A
350VA/210W
500VA/300W
500VA/300W
750VA/450W
approx. 5kg
approx. 5kg
approx. 5kg
approx. 9kg
287 x 287 x 45
287 x 287 x 45
287 x 287 x 45
90 x 287 x 278
10W
10W
10W
10W
5 minutes or more 3.5 minutes or more 3.5 minutes or more
5 minutes or more
Battery fully charged and with no condensation / 12 hours
Waveform
(In Commercial Powe
r Mode/
Batttery Mode)
Output capacity
(shared maximum)*1
Voltage *2
Switching time
Backup time*3
Type
Charging time
Operating ambient temperature
Operating ambient humidity
Full-time commercial power supply method
PC, display, and peripherals
50/60Hz
±
4Hz
Sine wave / Rectangular wave
10 msec. or less
Compact sealed lead battery
0 to 40
°
C (during operation)/ -15 to 40
°
C (during storage)
25 to 85%RH (during operation)/10 to 90%RH (during storage)
Input
Output
Battery
Environment
External dimensions
(W x D x H mm)
Weight of UPS
Internal power consumption
(Normal, Max.)
*1: Do not use the UPS exceeding allowable connection capacity either in VA or W values specified in the specifications.
*2: Do not fail to confirm the system operation beforehand if the unit is used other than "Output 100V mode".
At the time of battery operation, the maximum voltage may be lower than the voltage at the time of usual
operation (commercial power supply).
Rectangular waveforms during backup operation take the following values.
*3: At the rated load connection, 20
°
C, initial characteristics
BX35F/BX50F/BX50FW
BX75SW
100V mode
90V
103V
90V
115V
110V mode
100V*
103V*
100V
115V
115V mode
105V*
103V*
105V
115V
120V mode
105V*
103V*
105V
115V
*: The figures at 110V/115V/120V modes are effective only to BX50FW.
The minimum
voltage of the
effective value
The minimum
voltage of the
peak voltage
The minimum
voltage of the
effective value
The minimum
voltage of the
peak voltage
Peak voltage
100V mode
86 + 4 to 114
+ 4
VAC
110V mode
96 + 4 to 124
+ 4
VAC
115V mode
101 + 4 to 129
+ 4
VAC
120V mode
106 + 4 to 134
+ 4
VAC
100V mode
86 + 4 to 114
+ 4
VAC
110V mode
96 + 4 to 124
+ 4
VAC
115V mode
101 + 4 to 129
+ 4
VAC
120V mode
106 + 4 to 134
+ 4
VAC