23
2. Installation and connection
2-4 Checking the operation
When you are complete with connecting devices to the unit, the backup function must be confirmed.
Check that the Battery Mode is performed normally according to the following procedure.
This operation check simulates a power failure by disconnecting the AC input plug from a wall outlet.)
(1) Turn on the Power Switch of this unit.
The beeper sounds and the current settings are displayed on the LED.
After 5 secounds, the self-diagnostic test is performed in Battery Mode for approximately 10 seconds.
When the self-diagnostic test finishes successfully, switching to AC output from commercial power is per-
formed and the following display is obtained.
(If the battery voltage is low, the self-diagnostic test is not performed and the operation starts immediately,
using output from commercial power.)
(2) Bring all the connected devices into operation.
(Including devices connected to the AC outlet of your PC.)
Operate the devices in a way in which abrupt power stop does not damage the connected devices, data,
etc.
(3) Under this condition, check the LED display and a beep of this unit.
Are they in the same status as shown below?
Are the same as shown above.
➜
The operation is normal. Proceed to (4).
Are not the same as shown above.
➜
The operation is abnormal. One of the description in "4. Display
and beeps when there is an equipment failure" of "4-3 Interpreting
a beep and display" on page 29 must apply.
Take necessary measures and then proceed to (4).
(4) Disconnect the AC input plug of this unit from a wall outlet (commercial power).
The UPS enters Battery Mode.
Status indicator
Description
Power switch “ON”
Operating normally
Status indicator
Beep
Power supply output receptacles
None
Outputs power (connected devices are powered)