NV-series PT Simple Operation Handbook
Advanced UsageAdvanced Usage
Ct
i
it
h
Connecti
n
g w
ith
CPIE PLC
Designing Screens
Preparation
Setting the NV Communications
Set the NV - CP1E communications as the screen data.
Setting the NV communications
1. Select
PT
–
NV Configuration
from the menu bar.
Click!!
NV-CP1E communications setting example
The CP1E communications was set as follows. Set the same for the NV communications.
Mode: Host
Link
Baud rate:
115,200 bps
Data length:
7
Stop bit:
1
Parity bit:
Even
The stop bit for the NV serial communications is fixed to 1.
Therefore, the stop bit of the PLC serial port must be changed from the default 2 to 1.
2. Select the
Communication Parameters
Tab. Set the communications with the CP1E.
Click the
OK
Button to close the dialog box. This completes the NV communication setting.
Click!!
Set these items for
communications with the
CP1E.
Designing Screens
15