Appendix A
Device Protocol
112
DeviceNet Object (0x03)
Object class
Attribute
Not supported
Service
Not supported
Item
ID content
Get (read)
Set (write)
Value
Object instance
Attribute
1 MAC ID
Yes
No
---
2 Baud rate
Yes
No
---
3 BOI
Yes
No
00 (hexadecimal)
4 Bus Off counter
Yes
No
---
5 Allocation information
Yes
No
---
Item
DeviceNet service
Parameter option
Object instance
Service
0E Get_Attribute_Single
No
4B Allocate Master/Slave_Connection_Set
No
4C Release_Master/Slave_Connection_Set
No
Connection Object (0x05)
Object class
Attribute
Not supported
Service
Not supported
Max. number of active connections
1
Item
Section
Information
Max. number of instances
Object instance 1
Instance type
Explicit Message
1
Production trigger
Cyclic
---
Transport type
Server
Transport class
3
Item
ID content
Get
(read)
Set
(write)
Value
Object instance 1
Attribute
1 State
Yes
No
---
2 Instance type
Yes
No
00 (hexadecimal)
3 Transport class trigger
Yes
No
83 (hexadecimal)
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. characteristics
Yes
No
21 (hexadecimal)
7 Produced connection size
Yes
No
F0 (hexadecimal)
8 Consumed connection size
Yes
No
F0 (hexadecimal)
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
01
13 Produced connection path length
Yes
No
00
14 Produced connection path
Yes
No
---
15 Consumed connection path length
Yes
No
00
16 Consumed connection path
Yes
No
---
17 Production inhibit time
Yes
No
00
Item
DeviceNet service
Parameter option
Object instance 1
Service
05 Reset
No
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No