5-3
Section
Initializing DeviceNet (CompoBus/D) Memory Switches
58
Press Memory Switch.
Press CompoBus/D Setting Switch.
Press Yes.
The memory switches for the DeviceNet Inter-
face Unit will be initialized. The message Ini-
tializing will be displayed while initialization is
in progress.
When initialization is completed, a message
will be displayed and then the reset screen will
be displayed.
Press Reset.
The PT will be reset and will restart.
If No is pressed in the CompoBus/D setting switch initialization screen, the
switch settings will not be initialized and the PT will return to the Memory Init.
menu.
The following table shows the default settings that will be set when the Compo-
Bus/D setting switches are initialized.
Item
Meaning
Setting
Comm. speed
Communications speed
125 kbps
Self-node No.
Local node number
63
Strobe ON Time
Strobe ON time
30
OUT Area Head
Output area starting address
PM0000
OUT Area Size
Output area size
32
IN Area Head
Input area starting address
PM0032
IN Area Size
Input area size
32