Appendix A
Device Protocol
113
Item
Section
Information
Max. number of instances
Object instance 2
Instance type
Polled I/O
1
Production trigger
Cyclic
---
Transport type
Server
Transport class
2
Item
ID content
Get
(read)
Set
(write)
Value
Object instance 2
Attribute
1 State
Yes
No
---
2 Instance type
Yes
No
01 (hexadecimal)
3 Transport class trigger
Yes
No
82 (hexadecimal)
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. characteristics
Yes
No
01 (hexadecimal)
7 Produced connection size
Yes
No
(See note)
8 Consumed connection size
Yes
No
(See note)
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
01
13 Produced connection path length
Yes
No
00
14 Produced connection path
Yes
No
00_00_00_00_00_00
15 Consumed connection path length
Yes
No
00
16 Consumed connection path
Yes
No
00_00_00_00_00_00
17 Production inhibit time
Yes
No
00
Item
DeviceNet service
Parameter option
Object instance 2
Service
05 Reset
No
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No
Note The following table shows the settings for the sizes (number of bytes) of the input area and output area. The
actual setting format is 2 bytes with the leftmost byte and rightmost byte (values shown in following table)
reversed.
Attribute
Size
Value
Produced connection size
Input area: 0 to 64 bytes
00 to 40 (hexadecimal)
Consumed connection size
Output area: 0 to 64 bytes
00 to 40 (hexadecimal)
Item
Section
Information
Max. number of instances
Object instance 3
Instance type
Bit strobed I/O
1
Production trigger
Cyclic
---
Transport type
Server
Transport class
2