Alert Statements in this manual
2
!WARNING
Make sure to install the MS4800 system at the safe distance from the hazard-
ous part of the equipment. Otherwise, the machine may not stop before a per-
son reaches the hazardous part, resulting in serous injury.
!WARNING
Install a protective structure so that the hazardous part of a machine can only
be reached by passing through the sensor's detection zone. Install the sen-
sors so that part of the person is always present in the detection zone when
working in a machine's hazardous areas. If a person is able to step into the
hazardous area of a machine and remain behind the MS4800 system's detec-
tion zone, configure the system with an interlock function that prevents the
machine from being restarted. Failure to do so may result in serious injury.
!WARNING
Install the interlock reset switch in a location that provides a clear view of the
entire hazardous area and where it cannot be activated from within the haz-
ardous area.
!WARNING
The MS4800 system cannot protect a person from a projectile exiting the haz-
ardous zone. Install protective cover(s) or fence(s).
!WARNING
To prevent personnel approach to dangerous part of the machine through a
zone disabled by the fixed blanking function, you must install a protective
structure to cover the whole disabled zone. Failure to do so may cause failure
of human body detection, resulting in a serious injury.
!WARNING
You must ensure that a test rod is detected for all detection zones except
where fixed or floating blanking function is used. Failure to do so may cause
failure of human body detection, resulting in a serious injury.
!WARNING
Detection capability gets larger if fixed or floating blanking function is used.
You must use the detection capability for fixed and floating blanking functions.
Failure to do so may cause failure of machine stop before reaching the
machine's dangerous part, resulting in a serious injury.
!WARNING
The muting and override functions disable the safety functions of the device.
You must ensure safety using other method when these functions are operat-
ing.
!WARNING
Install muting sensors so that they can distinguish between the object that is
being allowed to pass through the detection zone and a person. If the muting
function is activated by the detection of a person, it may result in serious
injury.
!WARNING
Muting lamps (external indicators) that indicate the state of the muting and
override functions must be installed where they are clearly visible to workers
from all the operating positions.
!WARNING
Muting related time must be properly configured for its application by a suffi-
ciently trained and qualified person, and the person must have responsibility
for settings, especially when setting the muting time limit to infinite.
!WARNING
Use independent 2 input devices for muting inputs.
!WARNING
You must install MS4800 system muting sensor, and physical barrier, and con-
figure time settings for muting so that an operator should not enter hazardous
zone.
Summary of Contents for MS4800E
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 20: ...2 Section...
Page 26: ...8 MS4800FS Cascaded Series Section 4 3...
Page 34: ...16 Optical Synchronization Section 5 4...
Page 40: ...22 Selecting Scan Codes Section 7 7...
Page 42: ...24 Auxiliary Output Section 8 2...
Page 52: ...34 General Mounting Considerations Section 10 3...
Page 56: ...38 Connection to a safety relay unit Section 11 3...
Page 60: ...42 Using the test object Section 13 3...
Page 62: ...44 Section...
Page 88: ...70 Accessories Section 15 9...
Page 90: ...72 Section...
Page 97: ...79 EC Declaration of Conformity Section 18 3 18 3 EC Declaration of Conformity...