10 C
ONNECTING
T
O
T
HE
M
ACHINE
C
ONTROL
C
IRCUIT
10
WARNING!
This product is designed for use on a 24 VDC, negative ground (protective earth)
electrical system only. Never connect the MS4800 system to a positive ground (protective earth)
system. With a positive ground (protective earth) wiring scheme, certain simultaneous shorts of
both safety outputs may not be detected and the guarded machine may not stop, resulting is
severe operator injury.
WARNING!
Never use only a single safety output to control the machine. Should this single
output fail, the machine may not stop, resulting in severe operator injury. The machine must be
connected using both safety outputs.
▲
!
▲
!