Checking Operation

Overvoltage
Gradually increase the input from 80% of the set value. The 
input will equal the operating value when the input exceeds 
the set value and the alarm indicator starts flashing. 
Operation can be checked by the relay output that will start 
after the operating time has passed.
Undervoltage
Gradually decrease the input from 120% of the set value and 
check the operation using the same method as for an 
overvoltage.

How to Measure the Operating Time

Overvoltage
Change the input suddenly from 70% to 120% of the set value 
and measure the time until the Unit operates.
Undervoltage
Change the input suddenly from 120% to 70% of the set value 
and measure the time until the Unit operates.
Operating Time
Adjust the slide resistor so that the voltage applied to the 
K8DT terminals is 120% of the set value for overvoltage 
detection or 80% of the set value for undervoltage detection 
when the auxiliary relay in connection diagram 2 operates. 
Close the switch and use a cycle counter to measure the 
operating time.

Checking the Phase Sequence and Phase Loss 
Operation

Phase Sequence
Switch the wiring, as shown by the dotted lines in connection 
diagram 1, to reverse the phase sequence and check that the 
K8DT operates.
Phase loss
Create a phase loss for any input phase and check that the 
K8DT operates.

Questions and Answers

Q

Input voltage

Operating set value

Alarm indicator

Flashing

5 s

Lit

Contact output or 

transistor output

V3

V1

V2

3-phase, 
200 VAC

0 to 150 V

3-phase variable autotransformer

L1

L2

L3

L1

L2

L3

Example: Monitoring Mode for Rated Voltage of 200 V and an Operating 
Time Setting of 5 s

Connection Diagram 1

Q

V3

V1

V2

3-phase, 200 VAC

X/a

X/b

R1

R1: Sliding resistor, 200 

Ω

, 200 W

R2: 100 

Ω

, 400 W

R2

L1

L2

L3

L3

L2

L1

±

C 200 V

Cycle counter

X

Connection Diagram 2

Q

Summary of Contents for K8DT-PM

Page 1: ...h America Certification is pending for LR standards Models added with transistor outputs for superior contact reliability RoHS compliant Ordering Information Three phase Voltage and Phase sequence Pha...

Page 2: ...bient operating humidity 25 to 85 RH with no condensation Storage humidity 25 to 85 RH with no condensation Altitude 2 000 m max Applicable wires Stranded wires solid wires or ferrules Applicable wire...

Page 3: ...nd after an incorrect phase is detected and once per 0 5 second during the detection time K8DT PM1 C N L1 14 L2 11 12 L3 DIP SW Inside Inside 2 Output C Relay Output T Transistor Output 14 11 12 14 11...

Page 4: ...ck See Note Terminal block See Note Power indicator Output status indicator Overvoltage knob OVER Undervoltage knob UNDR Operating time knob T Alarm indicator 8 mm 8 mm Solid Wire 8 mm Stranded Wires...

Page 5: ...R The undervoltage can be set to between 30 and 30 of the rated input Turn the knob while there is an input to the input terminals until the alarm indicator flashes when the set value and the input ha...

Page 6: ...0 Three phase Voltage and Phase sequence Phase loss Relays K8DT PM1 K8DT PM2 Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parentheses...

Page 7: ...rminals is 120 of the set value for overvoltage detection or 80 of the set value for undervoltage detection when the auxiliary relay in connection diagram 2 operates Close the switch and use a cycle c...

Page 8: ...tected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load phase loss during operation use the undervoltage dete...

Page 9: ...alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay regularly To maintain s...

Page 10: ...e terminal block may be damaged 25 Insert a flat blade screwdriver into the release holes at an angle The terminal block may be damaged if the screwdriver is inserted straight in 26 Do not allow the f...

Page 11: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Page 12: ...maximum applied voltage for the clearance solid insulation and other factors There is basic insulation between the input terminals and output terminals Operating section must have reinforced or doubl...

Page 13: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 14: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Reviews: