K8DT-AS

3

Ratings

Specifications

*

K8DT-AS

@

TD is not applied.

Power supply voltage

K8DT-AS

@@

D: 24 VAC 50/60 Hz, 24 VDC

K8DT-AS

@@

A: 100 to 240 VAC 50/60 Hz

Power consumption

24 VAC/DC: 1.8 VA/1 W max.
100 to 240 VAC: 2.5 VA max.

Rated insulation 
voltage

600 VAC

Operating value 
setting range (SV)

10% to 100% of the maximum value of the setting range
K8DT-AS1: 2 to 20 mA AC/DC

10 to 100 mA AC/DC
50 to 500 mA AC/DC

K8DT-AS2: 0.1 to 1 A AC/DC (Compatible with 

commercially available CTs.)
0.5 to 5 A AC/DC (Compatible with 
commercially available CTs.)

K8DT-AS3: When used with the OMRON CT 

(K8AC-CT200L).
10 to 100 A AC
20 to 200 A AC

Operating value

100% operation at set value

Reset value setting 
range (HYS)

5% to 50% of operating value

Reset method

Manual reset/automatic reset (switchable)

Note:

Manual reset: Turn OFF power supply for 

1 s or longer.

Operating time 
setting range (T)

0.1 to 30 s

Startup lock time 
setting range (LOCK)

0 to 30 s
(The startup lock timer starts when the input has 
reached approximately 30% or more of the set value.)

Note:

Enabled only for overcurrent operation.

LED Indicators

Power (PWR): Green, Output (OUT): Yellow, 
Alarm outputs (ALM): Red

Input impedance

Refer to 

Input Range

 on page 2.

Output form

Relay Output: SPDT contact
Transistor Output: 1
Switchable between normally open and normally 
closed with a DIP switch setting.

Output relay ratings

Rated load: 250 VAC 5 A or 30 VDC 5 A 

(resistive load), 
250 VAC 1 A (inductive load), 
48 VDC 0.2 A (inductive load)

Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 

operations
3 A at 250 VAC or 30 VDC:100,000 
operations

Transistor output 
ratings

Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC

Ambient operating 
temperature

20 to 60°C (with no condensation or icing)

Storage temperature

25 to 65°C (with no condensation or icing)

Ambient operating 
humidity

25% to 85%

 

RH (with no condensation)

Storage humidity

25% to 85%

 

RH (with no condensation)

Altitude

2,000 m max.

Applicable wires

Stranded wires, solid wires, or ferrules

Applicable wire size

0.25 to 1.5 mm

2

 (AWG24 to AWG16)

Wire insertion force

8 N max. for AWG20 wire

Screwdriver 
insertion force

15 N max.

Wire stripping length

8 mm

Ferrule length

8 mm

Recommended flat-
blade screwdriver

XW4Z-00B (Omron)
SZF 0.4 

×

 2.5 (Phoenix Contact)

210-719 (Wago)
SDI 0.4 

×

 2.5 

×

 75 (Weidmuller)

Current capacity

10 A (per pole)

Number of insertions

50 times

Case color

N1.5

Case material

PC, UL 94 V-0

Weight

Approx. 100 g

Mounting

Mounts to DIN Track, or screw mounting

Dimensions

17.5 

×

 90 

×

 90 mm (W

×

H

×

D)

Allowable operating 
voltage range

85% to 110% of power supply voltage

Allowable operating 
frequency range

50/60 Hz 

±

5 Hz

Input frequency range

K8DT-AS1 and K8DT-AS2:DC input or AC input 

(45 to 65 Hz)

K8DT-AS3: AC input (45 to 65 Hz)

Overload capacity

K8DT-AS1 and K8DT-AS2:

Continuous input at 120% of 
maximum input, 1 s at 150%

K8DT-AS3:Continuous input at 120%, 30 s at 

200%, and 1 s at 600% with an 
OMRON CT (K8AC-CT200L)

Note:

Overload capacity of primary side of CT.

Repeat error

Operating 
value

±

0.5% full scale (at 25

°

C and 65% humidity, rated 

power supply voltage)

Operating 
time

±

50 ms (at 25

°

C and 65% humidity, rated power 

supply voltage)

Applicable 
standards

Conforming 
standards

EN 60947-5-1
Installation environment (pollution level 2, 
Overvoltage category III)

EMC

EN 60947-5-1

Safety 
standards

UL 60947-5-1 (Listing), Korean Radio Waves Act 
(Act 10564), CCC (GB/T 14048.5) 

*

Insulation resistance

20 M

Ω

 min.

Between external terminals and case
Between power supply terminals and input 
terminals
Between power supply terminals and output 
terminals
Between input terminals and output terminals

Dielectric strength

2,000 VAC for one minute

Between external terminals and case
Between power supply terminals and input 
terminals
Between power supply terminals and output 
terminals
Between input terminals and output terminals

Impulse withstand 
voltage

6 kV (between live terminals and exposed, 
non-charged metal parts)

Noise immunity 

Square-wave noise of 1-

μ

s/100-ns pulse width 

with 1-ns rise time
100 to 240 VAC:  1,500 V power supply terminal 

common/normal mode

24 VAC: 1,500 V power supply terminal common/

normal mode

24 VDC: 480 V power supply terminal common

Vibration resistance

Frequency 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X, Y, and Z directions

Shock resistance

100 m/s

2

, 3 times each in 6 directions along 3 axes

Degree of protection

Terminals: IP20

Summary of Contents for K8DT-AS Series

Page 1: ...ommercially available CT do not exceed the overload capacity of the K8DT AS2 Options Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions Fo...

Page 2: ...DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 Direct input 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 Direct input...

Page 3: ...Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Recommended flat blade screwdriver XW4Z 00B Omron SZF 0 4 2 5 Phoenix Co...

Page 4: ...copper wires with a rating of 75 C or an equivalent rating Inside Inside 1 Current Input AS1 2 Output C Relay Output T Transistor Output 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarit...

Page 5: ...1 s Power supply voltage Contacts 11 12 Set value Alarm indicator Lit Contacts 11 14 or transistor output Input Delay time 250 ms reference value Terminal block See note Terminal block See note Curren...

Page 6: ...itch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range Input type Wiring connections K8DT AS1 2 to 20 mA AC DC Direct input I1...

Page 7: ...et Value SV of 50 and Overcurrent Operation Operation will be at 100 A and resetting at 90 A when the hysteresis HYS is set to 10 Operating Time The operating time is set using the operating time knob...

Page 8: ...3 1 7 1 7 9 3 76 Two M5 screw holes or two 5 5 dia holes OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AS3 Use terminals k an...

Page 9: ...ely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AS1 and K8DT AS2 and result in failure of the Relay To monitor the motor load use the K8DT AS3 Overload ca...

Page 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Page 11: ...ck the wiring before you supply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When...

Page 12: ...e flat blade screwdriver from the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal...

Page 13: ...n and other factors There is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic in...

Page 14: ...MEMO 14...

Page 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 16: ...9 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyo...

Reviews: