2

Temperature Monitoring Relay

 

K8AB-TH

Specifications

Ratings

Characteristics

Item

Power supply voltage

100 to 240 VAC 50/60 Hz

24 VAC 50/60 Hz or 24 VDC

Allowable voltage range

85% to 110% of power supply voltage 

Power consumption

5 VA max.

2 W max. (24 VDC), 4 VA max. (24 VAC)

Sensor inputs

K8AB-TH11S

Thermocouple: K, J, T, E; Platinum-resistance thermometer: Pt100

K8AB-TH12S

Thermocouple: K, J, T, E, B, R, S, PLII

Output relay

One SPDT relay (3 A at 250 VAC, resistive load) 

External inputs 
(for latch setting)

Contact input

ON: 1 k

 max., OFF: 100 k

 min. 

Non-contact input

ON residual voltage: 1.5 V max., OFF leakage current: 0.1 mA max.

Leakage current: Approx. 10 mA

Setting method

Rotary switch setting (set of three switches)

Indicators

Power (PWR): Green LED, Relay output (ALM): Red LED 

Other functions

Alarm Mode (upper limit/lower limit), non-fail safe/fail safe selection, output latch, setting protection, temperature 
unit 

°

C/

°

Ambient operating temperature

10 to 55

°

C (with no condensation or icing)

Ambient operating humidity

Relative humidity: 25% to 85%

Storage temperature

25 to 65

°

C (with no condensation or icing)

Setting accuracy

±

2.0% of full scale

hysteresis width

2

°

C

Output relay

Resistive load

3 A at 250 VAC (cos

φ

 = 1), 3 A at 30 VDC (L/R = 0 ms)

Inductive load

1 A at 250 VAC (cos

φ

 = 0.4), 1 A at 30 VDC (L/R = 7 ms)

Minimum load

10 mA at 5 VDC

Maximum contact voltage

250 VAC

Maximum contact current

3 A AC

Maximum switching capacity

1,500 VA

Mechanical life

10,000,000 operations

Electrical life

Make: 50,000 times, Break: 30,000 times

Sampling cycle

500 ms

Insulation resistance

20 M

 (at 500 V) between charged terminals and exposed uncharged parts

20 M

 (at 500 V) between any charged terminals (i.e., between input, output, and power supply terminals)

20 M

 (at 500 V) between contacts (open)

Dielectric strength

2,000 VAC 50/60 Hz for 1 min between charged terminals of different polarity

Vibration resistance

Vibration of 10 to 55 Hz and acceleration of 50 m/s

2

 for 5 min with 10 sweeps each in X, Y, and Z directions

Shock resistance

150 m/s

2

 (100 m/s

2

 for relay contacts) 3 times each in 6 directions in X, Y, and Z directions

Weight

130 g

Degree of protection

IP20

Memory protection

Non-volatile memory (number or writes: 200,000)

Safety 
Standards

Approved standards

EN 61010-1

Application standards

EN 61326 and EN 61010-1 (pollution level 2, overvoltage category II)

EMC

EMI: EN 

61326

Radiation Interference Field Intensity:  EN 55011 Group 1 Class A
Noise Terminal Voltage: 

EN 55011 Group 1 Class A

EMS:

EN 61326 

Immunity ESD: 

EN 61000-4-2:

4 kV contact discharge (level 2)
8 kV air discharge (level 3)

Immunity RF: 

EN 61000-4-3:

10 V/m, amplitude-modulated 
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3)

Immunity Burst: 

EN 61000-4-4:

2 kV power line (level 3)
2 kV output line (relay output) (level 4)
1 kV measurement line and I/O signal lines (level 4)

Immunity Conducted Disturbance:

EN 61000-4-6:

3 V (0.15 to 80 MHz) (level 3)

Immunity Surge:

EN 61000-4-5:

1 kV line-to-line: power line, output line 
(relay output) (level 2)
2 kV line-to-ground: power line, output line 
(relay output) (level 3)

Commercial Frequency 
Immunity Magnetic Field:

EN 61000-4-8:

30 A/m (50Hz) continuous time

Immunity Voltage Dip/Interrupting:

EN 61000-4-11: 0.5 cycle, 100% (rated voltage)

Terminal screw tightening torque

0.54 to 0.55 N·m

Crimp terminals

Two solid wires of 2.5 mm

2

 or two ferrules of 1.5 mm

2

 with insulation sleeves can be tightened together.

Case color

Munsell 5Y8/1 (ivory) 

Case material

ABS resin (self-extinguishing resin)

Mounting

Mounted to DIN Track or with M4 screws

Dimensions

22.5 

×

 100 

×

 90 mm (W 

×

 D 

×

 H)

Summary of Contents for K8AB-TH

Page 1: ...r of models by using multi input support for thermocouple or Pt100 sensor input Selecting Functions and Modes The following settings are provided alarm mode upper limit lower limit enable disable latc...

Page 2: ...s i e between input output and power supply terminals 20 M at 500 V between contacts open Dielectric strength 2 000 VAC 50 60 Hz for 1 min between charged terminals of different polarity Vibration res...

Page 3: ...ement 1 F Input K J T E B R S PLII Setting tempera ture range 1 800 1 700 1 600 1 500 1 400 1 300 1 200 1 100 1 000 900 800 700 600 500 400 300 200 100 0 1 800 1 700 1 700 1 300 1 300 850 600 400 100...

Page 4: ...Thermocouple Platinum resistance thermometer K8AB TH11S K8AB TH12S Note 1 The input power supply depends on the model 100 to 240 VAC or 24 VAC VDC no polarity 2 Wiring of the external input terminals...

Page 5: ...itoring Relay error See note 1 Item Usage Output latch reset button The output latch can be reset by pressing this button Enabled when latch is enabled See note 2 Alarm setting rotary switch Set each...

Page 6: ...l input terminal for at least 5 s The power indicator will flash when the protection is activated The protection function can be released by pressing the output latch reset button on the Temperature M...

Page 7: ...ring Relay Allow as much space as possible between the Temperature Monitoring Relay and devices that generate powerful high frequencies high frequency welders high frequency sewing machines etc or sur...

Page 8: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: