Three-phase Voltage Relay

 

K8AB-PW

Cat. No. N148-E1-01

Ordering Information

List of Models

Note: 1.

Three-phase 3-wire or 4-wire and the input range are switched using a switch.

2.

The power supply is shared with the rated input voltage.

Ratings and Specifications

Ratings

Three-phase Voltage Relay

Rated input (See note 2.)

Model

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8AB-PW1

3-phase 4-wire mode

115, 127, 133, 138 VAC

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8AB-PW2

3-phase 4-wire mode

220, 230, 240, 277 VAC

Rated input 
voltage

K8AB-PW1

Three-phase, three-wire mode: 200, 220, 230, 240 VAC
Three-phase, four-wire mode: 115, 127, 133, 138 VAC

K8AB-PW2

Three-phase, three-wire mode: 380, 400, 415, 480 VAC
Three-phase, four-wire mode: 220, 230, 240, 277 VAC

Operation 
(overvoltage and 
undervoltage)

Operating value setting 
range

Overvoltage = 

30% to 25% of maximum rated input voltage

Undervoltage = 

30% to 25% of maximum rated input voltage

Note: The rated input voltage is switched with a switch. 

Operating value

100% operation at set value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating time (T) Overvoltage/

undervoltage

0.1 to 30 s (Value when input rapidly changes from 0% to 120%.)

Power ON lock (LOCK)

1 s or 5 s (Value when input rapidly changes from 0% to 100%. The operating time is the shortest 
at this point.)

Setting accuracy

±10% of full scale

Time error

±10% of set value (Minimum error: 50 ms)

Input frequency

45 to 65 Hz

Input impedance

100 k

 min.

Indicators

Power (PWR): Green LED, Relay output (RY): Yellow LED, Alarm outputs (ALM1/2): Red LED

Output relays

Two SPDT relays (6 A at 250 VAC, resistive load) 
Normally closed operation (normally ON) (separate outputs possible for overvoltages and 
undervoltages)

Summary of Contents for K8AB-PW

Page 1: ...possible for overvoltages and undervoltages World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy wiring with ferrules 2 2 5...

Page 2: ...ltage and undervoltage Operating value setting range Overvoltage 30 to 25 of maximum rated input voltage Undervoltage 30 to 25 of maximum rated input voltage Note The rated input voltage is switched w...

Page 3: ...ged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1 ivory Case...

Page 4: ...22 21 Over voltage alarm Under voltage alarm Load The power supply is shared with the rated in put voltage Power indicator Relay status indicator Overvoltage knob OVER Undervoltage knob UNDER Operati...

Page 5: ...hase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PW1 200 VAC 115 VAC OFF OFF ON OFF 220 VAC 127 VAC OF...

Page 6: ...roduct 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board whose st...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: