4

Three-phase Voltage Relay

 

K8AB-PW

Cat. No. N148-E1-01

Connections

Wiring Diagram

Overvoltage and Undervoltage Operation Diagram

Note: 1.

The K8AB-PW output relay is normally operative.

2.

The power ON lock prevents unnecessary alarms from 
being generated during the instable period when the power 
is first turned on. There is no relay output during timer 
operation.

Nomenclature

Front

Indicators

Setting Knobs

T

T1

T

L1

L2

L3

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

T: Operating time (0.1 to 30 s)

T1: Power ON lock (1 s or 5 s)

Flashing

Lit

Flashing

Lit

Overvoltage alarm indicator

Undervoltage alarm indicator

Overvoltage relay

Undervoltage relay

Undervoltage setting value

Overvoltage 

setting value

Input

T: Operating time (0.1 to 30 s)

Input

Output

Output

N L1 L2 L3

N

L1

L2

L3

14

12

11

24

22

21

Over-
voltage 
alarm

Under-
voltage 
alarm

Load

The power 
supply is 
shared with 
the rated in-
put voltage.

Power indicator

Relay status indicator

Overvoltage knob (OVER)

Undervoltage knob (UNDER)

Operating time knob (T)

Alarm indicator

Item

Meaning

Power indicator (PWR: Green)

Lit when power is being 
supplied.

Relay status indicator (RY: Yellow) Lit when relay is operating 

(normally lit).

Alarm 
indicator 
(ALM: Red)

Overvoltage: Red

The indicator flashes to indicate 
the error status after the 
overvoltage has exceeded the 
threshold value while the 
operating time is being clocked.

Undervoltage: Red The indicator flashes to indicate 

the error status after the 
undervoltage has exceeded the 
threshold value while the 
operating time is being clocked.

Item

Usage

Overvoltage knob (OVER)

Used to set the voltage to 

30% to 25% 

of the rated input voltage.

Undervoltage knob 
(UNDER)

Used to set the voltage to 

30% to 25% 

of the rated input voltage.

Operating time knob (T)

Used to set the operating time to 0.1 to 
30 s.

Summary of Contents for K8AB-PW

Page 1: ...possible for overvoltages and undervoltages World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy wiring with ferrules 2 2 5...

Page 2: ...ltage and undervoltage Operating value setting range Overvoltage 30 to 25 of maximum rated input voltage Undervoltage 30 to 25 of maximum rated input voltage Note The rated input voltage is switched w...

Page 3: ...ged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1 ivory Case...

Page 4: ...22 21 Over voltage alarm Under voltage alarm Load The power supply is shared with the rated in put voltage Power indicator Relay status indicator Overvoltage knob OVER Undervoltage knob UNDER Operati...

Page 5: ...hase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PW1 200 VAC 115 VAC OFF OFF ON OFF 220 VAC 127 VAC OF...

Page 6: ...roduct 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board whose st...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: