Slim Relay
G3RV
13
Definition of Precautionary Information
Precautions for Safe Use
●
Transpporting
Do not use or store the G3RV in the following transporting.
of Doing so may result in damage, mulfunction, or detericration
of performance characteristics.
•
Conditions under which the G3RV will be exposed to water.
•
High temperatures or high humidity.
•
Without proper packing.
●
Operating and Strage Locations
Do not use or store the G3RV, in the following locations. Doing so
may result in damage, mulfunction, or detericration of
performance characteristic.
•
Locations subject to rain or water drops.
•
Locations subject to exposure to water, or oil, or chemicals.
•
Locations subject to high temperatures or high humidity.
•
Locations subject to ambient temperatures outside the range
from -30 to +100 centigrade.
•
Locations subject to relative humidity outside the range 45% to
85%.
•
Locations subject to corrosive or ammable gasses.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to barrier.
●
Handring
•
Must need an air convection for G3RV or the heat convection air
producess a heating on G3RV abnormal and causes a
short-circuit failure and burning.
•
Do not use the G3RV with terminal bending due to dropping etc.
Bent terminal may poorly tting electrical contacts, leading to
trouble.
•
Do not carry out the mounting work with hand stained with oil or
metal powder. Otherwise, trouble may be caused.
●
Mounting
•
Mount the G3RV in the speci ed orientation. If the G3RV is
mounted in any other orientation, abnormal heat generation
may cause output elements to short or may cause burning.
•
Be sure to prevent the ambient temperature from rising due to
the heat radiation of the G3RV. If the G3RV is mounted a panel,
install a fan so that the interior of the panel is fully inside
ventilated.
•
Be sure that the G3RV clicks into place when mounting it to DIN
Track. The G3RV may fall if it is not mounted correctly.
●
Wiring
•
Use a wire an adequate size for current to be applied. Abnormal
heating of wire may cause burning.
•
Do not use any wires with damaged sheaths. These may caus
electric shock leakage.
•
Con rm it wire for G3RV is not used in pipe or duct for high
voltage power supply.Induction will be generated and cause
malfunction or damages.
•
Be sure to conduct wiring with the power supply turned OFF.
Touching the terminals when they are charged may occationally
result in minor electric shock.
●
Using
•
Select a load within the rated range. Inappropriate load may
cause misoperation, trouble or burning.
•
Select the power supply within the rated frequency range.
Inappropriate power frequency may cause misoperation, trouble
or burning.
Precautions for Correct Use
●
G3RV uses electronics parts mounting on PCB, so that any
dropping and vibration, physical shock beyond the standard level
should beprevented, otherwise the initial characteristic will be not
injured.
●
Terminal screw must be tightened with regulation torque. Less
convection air produces a heating on G3RV abnormal and causes
a short-circuit failure and burning.
(M2.5, 0.4 N•m)
●
Do not supply a high voltage/current to the input and output. Short
circuit failure or burning must be occured on G3RV.
●
Do not use or store the G3RV, in the following locations. Doing so
may result in damage, malfunction, or deterioration of
performance characteristic.
•
Locations subject to static electricity or other forms of noise.
•
Locations subject to strong electromagnetic elds.
•
Locations subject to possible exposure to radioactivity.
WARNING
Indicates a potentially hazardous situation which,
if not avoided, will result in minor or moderate
injury, or may result in serious injury or death.
Additionally there may be significant property
damage.
CAUTION
A potentioally hazardous situation by misuse,
may result in property damage only accident.
CAUTION
Minor hazard by electric shock may occasionally occur.
Do not touch the G3RV's terminal (Charging part) while
the power supply turned on.
The G3RV may occasionally rupture in case of a short
circuit.
To protect against short-circuit accident, install a
protective device, such as a quick-burning fuse or a
circuit breaker or the like, on the power supply.
Minor hazard by electric shock may occasionally occur.
Do not touch the G3RV's main circuit terminals
immediately after the power is turned OFF.
The internal snubber circuit is charged.
*
202S,SL,G3RV-A(L) Type only
Minor hazard by burns may occasionally occur.
Do not touch the G3RV or the heat sink either while the
power supply is ON, or immediately after the power is
turned OFF.
The G3RV and the heat sink will be hot.