2
Slim Relay
G3RV
Specifications
■
Ratings (at an Ambient Temperature of 25°C)
Input
G3RV-SL700/500-A Series
G3RV-SL700/500-AL Series
G3RV-SL700/500-D Series
Output
Rated voltage
Rated current
Must operate
voltage
Must release
voltage
Input voltage
AC
DC
% of rated voltage
50 Hz
60 Hz
12 VDC
---
---
15 mA
10.8V
1V
±
10%
24 VDC
---
---
12 mA
21.6V
24 VAC/DC
20 mA
21 mA
11 mA
21.6V
48 VAC/DC
10 mA
11 mA
6 mA
43.2V
110 VAC
7.5 mA
8.2 mA
---
99V
230 VAC
7.3 mA
8.6 mA
---
207V
Rated voltage
Rated current
Must operate
voltage
Must release
voltage
Input voltage
AC
DC
% of rated voltage
50 Hz
60 Hz
12 VDC
---
---
15 mA
10.8V
1V
±
10%
24 VDC
---
---
12 mA
21.6V
24 VAC/DC
20 mA
21 mA
11 mA
21.6V
48 VAC/DC
10 mA
11 mA
6 mA
43.2V
110 VAC
7.5 mA
8.2 mA
---
99V
230 VAC
7.3 mA
8.6 mA
---
207V
Rated voltage
Rated current
Must operate
voltage
Must release
voltage
Input voltage
AC
DC
% of rated voltage
50 Hz
60 Hz
12 VDC
---
---
8 mA
10.8V
1V
±
10%
24 VDC
---
---
4.5 mA
21.6V
24 VAC/DC
10.7 mA
11.1 mA
4.3 mA
21.6V
48 VAC/DC
9.6 mA
10.2 mA
6 mA
43.2V
110 VAC
6.8 mA
7.5 mA
---
99V
230 VAC
6.8 mA
8.1 mA
---
207V
Item
G3RV-SL700/500-A(L)
G3RV-SL700/500-D
Rated load voltage
AC100~240V (50/60Hz)
DC5~24V
Load voltage range
AC75~264V (50/60Hz)
DC3~26.4V
Load current
0.1~2A (Ta=40°C)
100µA~3A (Ta=40°C)
Inrush current
30A (60Hz/1cycle)
30A (60Hz/1cycle)
Permissible I
2
t ; Joule Integral
(Reference value)
15A
2
s
9A
2
s
Application load capacity
400W
(Output voltage: AC200V)
72W
(Output voltage: DC24V)